Plan Review Notes
Plan Review Notes For Permit 14011386
Permit Number 14011386
Review Stop B
Sequence Number 1
Notes
Date Text
2014-01-23 18:00:19BUILDING PLAN REVIEW
 PERMIT: 14011386
 ADD: 1793 PALM BEACH LAKES # W411
 CONT: TO BE DETERMINED
 TEL: (561)373-3902
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY JAN. 23/2014
 ACTION: DENIED
  
 THE PERMIT APPLICATION WILL NEED TO BE UPDATED, UNDER
 THE DESCRIPTION OF WORK, ADDING STOCKROOM WALLS. PLEASE
 NOTE THIS SPACE IS A SHELL ONLY SPACE, THERE HAS NEVER
 BEEN A TENANT TO RECEIVE A CERTIFICATE OF OCCUPANCY.
 THIS IS A TENANT BUILD-OUT THAT WILL RECIEVE A
 CERTIFICATE OF OCCUPANCY.
  
  
 1) PB OUTLET MALLS:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER.
  
 2) VALUE IS LOW FOR THE AMOUNT OF WORK TO BE COMPLETED
 UNDER THE SCOPE OF THIS PERMIT. HOLD WILL BE PUT OM
 PERMIT UNTILS FEES ARE INCREASED.
  
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) PLEASE REVIEW SHEET LS01 EGRESS THRU STOCK ROOM SEE
 SECTION:
 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 EXCEPTIONS:
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA
 TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 4) PLANS ARE DEFICIENT, EGRESS PATHS CAN NOT BE CHECKED
 FOR COMPLIANCE WITH 2010 FBC-B 1017.3 AISLE ACCESSWAYS
 IN MERCANTILE OCCUPANCIES.
  
 5) PLANS ARE DEFICIENT, EGRESS PATHS CAN NOT BE CHECKED
 FOR COMPLIANCE SHOW ACCESSIBLE AISLES 2010 FL
 ACCESSIBILITY CODE 403.5.1.
  
 6) PLANS DO NOT PROVIDE ENOUGH INFORMATION AS TO IF
 EITHER TENANT SPACE WILL REQUIRE DRESSING ROOMS, IF IF
 SO THEN COMPLIANCE WITH 2010 FL ACCESSIBILITY CODE
 903.4.1-5.
  
 7) PLANS ALSO FAIL TO PROVIDE COMPLIANCE WITH 2010 FL
 ACCESSIBILITY CODE 904.3.2 ,904.4.1-2.
  
 8) WITH THE OCCUPANT LOAD FOR THIS TENANT, 2 RESTROOMS
 ARE REQUIRED, ONE OF THE RESTROOMS CAN BE COUNTED WITH
 THE COMMON RESTROOMS IN BUILDING J09, THE SECOND
 RESTROOM WILL STILL NEED TO COMPLY WITH 2010 FBC-P
 403.3.1 ACCESS.
 THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY
 SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES
 SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR
 OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO
 THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE
 BUILDING IS OCCUPIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]