2014-01-23 18:28:15 | BUILDING PLAN REVIEW |
| PERMIT: 14011385 |
| ADD: 1793 PALM BEACH LAKES # W409 |
| CONT: TO BE DETERMINED |
| TEL: (561)373-3902 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURSDAY JAN. 23/2014 |
| ACTION: DENIED |
| |
| THE PERMIT APPLICATION WILL NEED TO BE UPDATED, UNDER |
| THE DESCRIPTION OF WORK, ADDING STOCKROOM WALLS. PLEASE |
| NOTE THIS SPACE IS A SHELL ONLY SPACE, THERE HAS NEVER |
| BEEN A TENANT TO RECEIVE A CERTIFICATE OF OCCUPANCY. |
| THIS IS A TENANT BUILD-OUT THAT WILL RECIEVE A |
| CERTIFICATE OF OCCUPANCY. |
| |
| 1) PB OUTLET MALLS: |
| A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT |
| CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER. |
| |
| 2) VALUE IS LOW FOR THE AMOUNT OF WORK TO BE COMPLETED |
| UNDER THE SCOPE OF THIS PERMIT. HOLD WILL BE PUT OM |
| PERMIT UNTILS FEES ARE INCREASED. |
| |
| W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 3) PLEASE REVIEW SHEET LS01 EGRESS THRU STOCK ROOM SEE |
| SECTION: |
| 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES. |
| EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH |
| THIS SECTION. |
| 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| EXCEPTIONS: |
| 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE |
| FOLLOWING ARE MET: |
| 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| THAT FOUND IN THE MAIN RETAIL AREA; |
| 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| THROUGH THE STOCKROOM; |
| 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| EGRESS SIDE; AND |
| 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| TO THE EXIT WITHOUT OBSTRUCTIONS. |
| |
| 4) PLANS ARE DEFICIENT, EGRESS PATHS CAN NOT BE CHECKED |
| FOR COMPLIANCE WITH 2010 FBC-B 1017.3 AISLE ACCESSWAYS |
| IN MERCANTILE OCCUPANCIES. |
| |
| 5) PLANS ARE DEFICIENT, EGRESS PATHS CAN NOT BE CHECKED |
| FOR COMPLIANCE SHOW ACCESSIBLE AISLES 2010 FL |
| ACCESSIBILITY CODE 403.5.1. |
| |
| 6) PLANS DO NOT PROVIDE ENOUGH INFORMATION AS TO IF |
| EITHER TENANT SPACE WILL REQUIRE DRESSING ROOMS, IF IF |
| SO THEN COMPLIANCE WITH 2010 FL ACCESSIBILITY CODE |
| 903.4.1-5. |
| |
| 7) PLANS ALSO FAIL TO PROVIDE COMPLIANCE WITH 2010 FL |
| ACCESSIBILITY CODE 904.3.2 ,904.4.1-2. |
| |
| 8) WITH THE OCCUPANT LOAD FOR THIS TENANT, 2 RESTROOMS |
| ARE REQUIRED, ONE OF THE RESTROOMS CAN BE COUNTED WITH |
| THE COMMON RESTROOMS IN BUILDING J09, THE SECOND |
| RESTROOM WILL STILL NEED TO COMPLY WITH 2010 FBC-P |
| 403.3.1 ACCESS. |
| THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY |
| SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES |
| SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR |
| OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE |
| ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING |
| CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO |
| THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE |
| BUILDING IS OCCUPIED. |
| |