 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***PROVISO***
 PER NFPA 13: CHAPTER 8
 8.15.20.1* IN NEW INSTALLATIONS EXPECTED TO SUPPLY
 SPRINKLERS BELOW A CEILING, MINIMUM 1 IN. (25 MM)
 OUTLETS SHALL BE PROVIDED.
 8.15.20.2* IN NEW INSTALLATIONS, IT SHALL BE PERMITTED
 TO PROVIDE MINIMUM 1 IN. (25 MM) OUTLETS WITH HEXAGONAL
 BUSHINGS TO ACCOMMODATE SPRINKLERS ATTACHED DIRECTLY TO
 BRANCH LINE FITTINGS TO ALLOW FOR FUTURE SYSTEM
 MODIFICATIONS.
 8.15.20.4.2 ALL PIPING OTHER THAN THE NIPPLE PERMITTED
 IN 8.15.20.4.1 AND 8.15.20.4.3 SHALL BE A MINIMUM OF 1
 IN. (25 MM) IN DIAMETER.
  
 ADDITIONAL HEADS NEEDED TOWARDS CENTER OF TENANT SPACE.
 PLANS SHOW SPRINKLER HEADS THAT EXCEED THE 130 SQ FT.
 MAXIMUM.
  