Plan Review Notes For Permit 14011308 |
Permit Number |
14011308 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-01-25 14:18:53 | FUEL GAS PLAN REVIEW | | PERMIT: 14011308 | | ADD: 425 33RD ST | | CONT: ANYTIME COMPANIES, INC | | TEL: (561)969-3996 | | | | 2010 FLORIDA FUE GAS CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 1ST REVIEW | | DATE: SATURDAY JAN. 25/ 2014 | | ACTION: DENIED | | | | 1) SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | PIPE SIZES, 2010 FBC- FUEL GAS 402.3. | | | | 2) TYPE OF GAS, (LP OR NATURAL). | | | | 3) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) | | | | 4) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | PSI. | | | | 5) SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | FBC-2010 FUEL GAS SEC. 402.2. | | | | 6) MANUFACTURERS SPECIFICATION SHEETS TO IDENTIFY WHERE | | THE UNITS CAN OR CAN NOT BE INSTALLED, CLOSENESS TO | | DOORS, WINDOWS & SOFFITS. 503.4.2 SPECIAL GAS VENTS. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | | | | | | | |
|