Plan Review Notes
Plan Review Notes For Permit 14011279
Permit Number 14011279
Review Stop G
Sequence Number 2
Notes
Date Text
2014-01-27 06:02:1414011279
 INSTALATION OF NATURAL GAS LINE
 NATURAL
 0.5 PS
 TABLE 402.4(19)
 PRESSURE DROP O.5 IN. W.C.
 SPECIFIC GRAVITY 0.60
 METHOD: LONGEST LENGTH
 20'-0"
 3/4 " PE PIPE
  
 2010 FUEL GAS PROVISO:
 404.15.3 TRACER.
 A YELLOW INSULATED COPPER TRACER WIRE OR OTHER APPROVED
 CONDUCTOR SHALL BE
 INSTALLED ADJACENT TO UNDERGROUND NONMETALLIC PIPING .
 ACCESS SHALL BE PROVIDED
 TO THE TRACER WIRE OR THE TRACER WIRE SHALL TERMINATE
 ABOVE GROUND AT EACH END
 OF THE NONMETALLIC PIPING . THE TRACER WIRE SIZE SHALL
 NOT BE LESS THAN 18 AWG AND
 THE INSULATION TYPE SHALL BE SUITABLE FOR DIRECT
 BURIAL.
  