Plan Review Notes
Plan Review Notes For Permit 14011233
Permit Number 14011233
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-01-22 10:53:39PERMIT #14011233
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO
 PER NFPA 13: CHAPTER 8
 8.15.20.1* IN NEW INSTALLATIONS EXPECTED TO SUPPLY
 SPRINKLERS BELOW A CEILING, MINIMUM 1 IN. (25 MM)
 OUTLETS SHALL BE PROVIDED.
 8.15.20.2* IN NEW INSTALLATIONS, IT SHALL BE PERMITTED
 TO PROVIDE MINIMUM 1 IN. (25 MM) OUTLETS WITH HEXAGONAL
 BUSHINGS TO ACCOMMODATE SPRINKLERS ATTACHED DIRECTLY TO
 BRANCH LINE FITTINGS TO ALLOW FOR FUTURE SYSTEM
 MODIFICATIONS.
 8.15.20.4.2 ALL PIPING OTHER THAN THE NIPPLE PERMITTED
 IN 8.15.20.4.1 AND 8.15.20.4.3 SHALL BE A MINIMUM OF 1
 IN. (25 MM) IN DIAMETER.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved