2014-08-21 08:58:242010 FBC
  
 DENIED BY BUILDING
  
 1) THE NON-ENGINEERED FLOOD OPENINGS SPECIFIED ON
 SHEETS A-1 AND A-4 OF THE PLANS ARE ALL LOCATED ON THE
 SAME EXTERIOR WALL. FBCR322.2.2(2)(2.1) REQUIRES A
 MINIMUM OF TWO OPENINGS ON DIFFERENT SIDES OF EACH
 ENCLOSED AREA. PROVIDE OPENINGS ON ONE OF THE OTHER
 EXTERIOR WALLS. ONLY THE "NET OPEN AREA" OF THE
 NON-ENGINEERED OPENINGS CAN BE COUNTED TOWARD THE
 REQUIRED FLOOD OPENING AREA. THE MEASUREMENT OF THE NET
 OPEN AREA MUST TAKE INTO CONSIDERATION ANY COVERINGS
 THAT HAVE SOLID OBSTRUCTIONS, SUCH AS GRILLS, FIXED
 LOUVERS OR FACEPLATES.
  
 2) THE ROOFING PRODUCT APPROVALS THAT WERE SUBMITTED
 ARE FOR A CONCRETE DECK AND THIS PROJECT HAS A PLYWOOD
 ROOF DECK. THE PRODUCT APPROVALS ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD. SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR
 THE ROOFING MATERIALS THAT WILL BE USED AS REQUIRED BY
 DCA RULE 9N-3.
  