2014-07-03 11:37:04DATE: 7/3/2014
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) THE SMOKE/CARBON MONOXIDE DETECTORS SHOWN ON THE
 LANDING APPEAR TO BE OUT IN THE OPEN. NOT ONLY ARE
 THESE DEVICES NOT LISTED FOR OUTDOOR USE, BUT THEY ARE
 NOT NEEDED.
 2) A CORRECTION/ADDITION TO "NOTE 8" TO INCLUDE THE NEC
 314.27 REQUIREMENT STATING THAT THESE BOXES SHALL BE
 LISTED TO SUPPORT 50#.
 3) ADDITIONAL OUTLETS REQUIRED IN THE BEDROOMS TO MEET
 THE SPACING CRITERIA OF NEC 210.52
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,