2014-05-21 10:14:57THE FOLLOWING DEFICIENCIES WERE NOTED ON THE SECOND
 REVIEW:
  
 1. THE SMOKE/CARBON MONOXIDE DETECTORS SHOWN ON THE
 LANDING APPEAR TO BE OUT IN THE OPEN. NOT ONLY ARE
 THESE DEVICES NOT LISTED FOR OUTDOOR USE, BUT THEY ARE
 NOT DESIGNED FOR THE PURPOSE.
 2. A CORRECTION/ADDITION TO "NOTE 8" TO INCLUDE THE NEC
 314.27 REQUIREMENT STATING THAT THESE BOXES SHALL BE
 LISTED TO SUPPORT 50#.
 3. THERE SHALL BE A CARBON MONOXIDE DETECTOR OUTSIDE OF
 THE SLEEPING OF THE ROOMS AND WITHIN 10' OF THE DOOR AS
 PER FBC-R 315.
 4. ADDITIONAL OUTLETS REQUIRED IN THE BEDROOMS TO MEET
 THE SPACING CRITERIA OF NEC 210.52.
 5. INDICATE ON THE PLANS THE ACTUAL LOCATION OF THE
 ELECTRICAL PANELS. THERE IS A CONFLICT BETWEEN THE
 LOCATIONS INDICATED ON PAGES A-0 & E-1.
 6. PROVIDE LOAD CALCS IN ACCORDANCE WITH NEC 220.83(B).
 7. PROVIDE AN ACCURATE AND SITE SPECIFIC ELECTRICAL
 RISER DIAGRAM AND PANEL SCHEDULE.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.