Plan Review Notes
Plan Review Notes For Permit 14011176
Permit Number 14011176
Review Stop B
Sequence Number 2
Notes
Date Text
2014-05-29 11:10:582010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WITH A
 REQUIRED BASE FLOOD ELEVATION OF 7' NGVD. THE ELEVATION
 FOR THE FINISH FLOOR OF THE GARAGE IS SPECIFIED ON THE
 PLANS AS 5.74', WHICH DOES NOT COMPLY WITH THE CITY'S
 FLOOD ORDINANCE (6" ABOVE BFE). BECAUSE THE ADDITION OF
 A SECOND FLOOR TO THE GARAGE IS A SUBSTANTIAL
 IMPROVEMENT THE EXISTING GARAGE IS REQUIRED TO COMPLY
 WITH THE FLOOD ORDINANCE. THE FINISH FLOOR OF THE
 GARAGE CAN BE RAISED TO 7.5' NGVD. IF THE GARAGE IS
 USED SOLELY FOR THE PARKING OF VECHICLES, THE FINISHED
 FLOOR CAN BE BELOW THE BFE AND ENGINEERED FLOOD VENTS
 OR FLOOD OPENINGS CAN BE INSTALLED IN THE WALLS OF THE
 GARAGE ( SEE FEMA TECHINICAL BULLETIN 1 / AUGUST 2008 )
 OR SOME OTHER APPROVED METHOD MAY BE USED.
  
 2) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER/AGENT.
  
 3) THE ENERGY CALCULATION FORM LISTS THE INSULATION FOR
 THE FLOOR OVER THE GARAGE AS R-21.0 AND THE SECTIONS ON
 SHEET A-6 SPECIFY R-11 BATT INSULATION. PLEASE CORRECT.
  
 4) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 ROOFING MATERIALS THAT WILL BE USED AS REQUIRED BY DCA
 RULE 9N-3.
  
 5) THE VALUE OF $23,000.00 SPECIFIED ON THE PERMIT
 APPLICATION IS TOO LOW FOR THE SCOPE OF WORK SHOWN ON
 THE PLANS. CITY AMENDMENTS 109.3
  