Plan Review Notes
Plan Review Notes For Permit 14011176
Permit Number 14011176
Review Stop B
Sequence Number 1
Notes
Date Text
2014-03-07 18:19:392010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE. THE
 ELEVATION CERTIFICATE ON FILE FOR THE CONSTRUCTION OF
 THE SINGLE FAMILY DWELLING, PERMIT NUMBER 02100307,
 INDICATES THAT THE TOP OF THE LOWEST FLOOR IS 7.5'
 WHICH COMPLIES WITH THE CITY'S FLOOD ORDINANCE (6"
 ABOVE BFE).
  
 2) THE PLANS THAT WERE SUBMITTED ARE INCOMPLETE. THE
 STRUCTURAL SHEETS ARE NUMBERED S-6, S-7 AND S-8. SHEETS
 S-1 THRU S-5 ARE MISSING. SUBMIT TWO SETS OF ELEVATION
 DRAWINGS AND A SITE PLAN SHOWING THE LOCATION OF THE
 STRUCTURES ON THE LOT. CITY AMENDMENTS 107.2.1
  
  
 3) THE STRUCTURE IS LOCATED ON THE INTERCOASTAL
 WATERWAY MAKING IT EXPOSURE CATEGORY D. PLEASE CORRECT
 THE EXPOSURE CATEGORY AND THE WIND PRESSURES IN THE
 SCHEDULE ON SHEET S-6. FBC R301.2.1.4
  
 4) THE SCOPE OF WORK SHOWN ON THE PLANS IS NOT CLEAR.
 PLEASE PROVIDE A COMPLETE LIST OF THE WORK THAT IS TO
 BE DONE UNDER THIS PERMIT. CITY AMENDMENTS 107.2.1
  
 5) THERE ARE NOT AND GUARDS SHOWN ON THE DRAWINGS FOR
 THE STAIRS, THE WALKWAY OR THE ROOF DECK. SHOW
 COMPLIANCE WITH FBC R312.
  
 6) SHOW COMPLIANCE WITH FBC R311.7.7 FOR THE REQUIRED
 HANDRAILS.
  
 7) FROM THE INFORMATION PROVIDED ON SHEET S-6, IT
 APPEARS THAT NEW WINDOWS ARE BEING INSTALLED INTO NEW
 OPENINGS INTO THE GARAGE WALLS. PLEASE CLARIFY.
  
 8) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE NEW
 EXTERIOR DOOR WITH SIDELIGHT, THE ROOFING MATERIAL THAT
 WILL BE INSTALLED ON THE GARAGE ROOF DECK AND THE
 ELEVATED WALKWAY ( PLYWOOD), THE METAL CONNECTORS,
 ANCHORS AND HANGERS, THE NEW WINDOWS AND 8" STRUCTURAL
 LINTELS AS REQUIRED BY DCA RULE 9N-3.
  
 9) THE NEW WINDOWS WILL BE REQUIRED TO HAVE LARGE
 MISSILE IMPACT PROTECTION. FBCR 301.2.1.2 IF STORM
 PANELS ARE USED, SUBMIT TWO SETS OF PRODUCT APPROVALS
 FOR THEM. DCA RULE 9N-3
  
 10) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 PROJECT. CITY AMENDMENTS 107.3.4.1
  
 11) PROVIDE BUCK DETAILS FOR THE NEW DOOR AND WINDOW
 OPENINGS. FBCR612.10.2
  
 12) SUBMIT THE MANUFACTURER'S LOAD TABLES FOR THE 5-14"
 X 14" MICROLAM BEAMS. FBCR 301.1
  
 13) UPDATE THE ACI STANDARDS SPECIFIED ON SHEET S-8 TO
 THE 2008 EDITIONS. THIS IS THE EDITION THAT IS
 REFERENCED IN THE 2010 FBC. SEE CHAPTER 43.
  
 NOTE: IN ORDER TO SPEED REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]