2014-02-24 18:35:212010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF MECHANICAL PLANS FOR THE NEW
 ADDITIONS. SHOW THE LOCATIONS OF THE HEATING AND
 COOLING EQUIPMENT. SHOW THE LOCATIONS AND SIZES OF ALL
 SUPPLY AND RETURN DUCTS. SPECIFY THE GRILL SIZES AND
 CFMS AT EACH OF THE SUPPLY OUTLETS. CITY AMENDMENTS
 107.3.5.3
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT
 MATCHES THE EQUIPMENT SIZING CALCULATIONS. 107.2.1
  
 3) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED AIR
 RETURN.
  
 4) THE PLANS SHOW THE A/C CONDENSING UNITS LOCATED 12"
 OFF THE PROPERTY LINE. PLEASE BE AWARE THAT THE HEATING
 AND COOLING EQUIPMENT IS REQUIRED TO BE LOCATED TO
 PERMIT THE MAINTENANCE AND SERVICING OF THE EQUIPMENT,
 AS WELL AS, PROVIDING THE CLEARANCES REQUIRED BY THE
 MANUFACTURER. FBCR M1401.1 AND M1401.2.
  
 5) PROVIDE THE NAME, LICENSE NUMBER AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE MECHANICAL SYSTEM DESIGN
 ON THE PLANS. CITY AMENDMENTS 107.2.1 AND FS 471.003
  
  
  