Plan Review Notes For Permit 14011168 |
Permit Number |
14011168 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-02-24 18:35:21 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) SUBMIT TWO SETS OF MECHANICAL PLANS FOR THE NEW | | ADDITIONS. SHOW THE LOCATIONS OF THE HEATING AND | | COOLING EQUIPMENT. SHOW THE LOCATIONS AND SIZES OF ALL | | SUPPLY AND RETURN DUCTS. SPECIFY THE GRILL SIZES AND | | CFMS AT EACH OF THE SUPPLY OUTLETS. CITY AMENDMENTS | | 107.3.5.3 | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT | | MATCHES THE EQUIPMENT SIZING CALCULATIONS. 107.2.1 | | | | 3) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED AIR | | RETURN. | | | | 4) THE PLANS SHOW THE A/C CONDENSING UNITS LOCATED 12" | | OFF THE PROPERTY LINE. PLEASE BE AWARE THAT THE HEATING | | AND COOLING EQUIPMENT IS REQUIRED TO BE LOCATED TO | | PERMIT THE MAINTENANCE AND SERVICING OF THE EQUIPMENT, | | AS WELL AS, PROVIDING THE CLEARANCES REQUIRED BY THE | | MANUFACTURER. FBCR M1401.1 AND M1401.2. | | | | 5) PROVIDE THE NAME, LICENSE NUMBER AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE MECHANICAL SYSTEM DESIGN | | ON THE PLANS. CITY AMENDMENTS 107.2.1 AND FS 471.003 | | | | | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|