2014-02-27 19:07:26 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) THE SURVEY THAT WAS SUBMITTED INCORRECTLY SPECIFIES |
| THE PROPERTY AS BEING FLOOD ZONE B AND A-5. ACCORDING |
| TO THE FLOOD INSURANCE RATE MAP ON FILE WITH THE CITY |
| THIS PROPERTY IS LOCATED IN FLOOD ZONE B ONLY. SUBMIT |
| TWO COPIES OF A CORRECTED SURVEY. |
| |
| 2) THIS STRUCTURE IS LOCATED WITHIN 600 FEET OF THE |
| INTER-COASTAL WATERWAY AND IS CONSIDERED EXPOSURE |
| CATEGORY D. PLEASE CORRECT THE WIND DESIGN DATA AND THE |
| WIND PRESSURES ON SHEET S1.00 AND SPECIFY THE MEAN ROOF |
| HEIGHT AND ROOF SLOPE OF THE STRUCTURE ON THE PLANS. |
| |
| 3) SHOW COMPLIANCE WITH FBC R310 FOR EMERGENCY ESCAPE |
| AND RESCUE OPENINGS FOR SECOND FLOOR BEDROOMS #2 AND |
| #3. |
| |
| 4) WALL SECTION C ON SHEET A.07 APPEARS TO SHOW AN |
| UN-VENTED ATTIC WITH THE INSULATION ON THE TOP CORD |
| WITH NO SOFFIT VENTS FOR ATTIC VENTILATION SHOWN. THE |
| ENERGY CALCULATIONS SPECIFY A VENTED ATTIC. PLEASE |
| CLARIFY. IF THE ATTIC IS UN-VENTED PROVIDE TWO COPIES |
| OF THE PRODUCT EVALUATIONS FOR THE SPRAY FOAM |
| INSULATION THAT WILL BE USED. IF THE ATTIC IS VENTED |
| SPECIFY THE SIZE AND SPACING OF THE VENTS. CITY |
| AMENDMENTS 107.2.1, FBC R806 |
| |
| 5) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED |
| AND DATED BY THE PREPARER AND THE OWNER/AGENT. FBC |
| ENERGY CONSERVATION 405.4 |
| |
| 6) SPECIFY THE WINDOW TYPES, SIZES AND LOCATIONS ON THE |
| PLANS FOR THE WINDOWS THAT WILL BE REPLACED. CITY |
| AMENDMENTS 107.2.1, FBC R301.2.1, R310 |
| |
| 7) INDICATE THE WINDOWS THAT WILL BE CONNECTED TOGETHER |
| WITH THE STRUCTURAL MULLIONS. CITY AMENDMENTS 107.2.1, |
| FBC R301.2.1 |
| |
| 8) TAKE NOTE OF THE SOIL REPORT RECOMMENDATIONS AND |
| COORDINATE INSPECTIONS WITH THE STRUCTURAL BUILDING |
| INSPECTOR. |
| |
| 9) NOTE: THE WOOD FENCE AND GATE SHOWN ON THE PLANS |
| REQUIRE SEPARATE APPLICATION, PERMIT AND REVIEWS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |