Plan Review Notes For Permit 14010967 |
Permit Number |
14010967 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-01-21 09:14:11 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) A SEPARATE PERMIT APPLICATION, PLANS AND REVIEW IS | | REQUIRED FOR MECHANICAL WORK. THIS WAS SPECIFIED IN THE | | CONSTRUCTION SERVICES STAMP ON THE LETTER FROM J.B. | | KERN INDICATING THE SCOPE OF WORK THAT AS SUBMITTED TO | | OBTAIN PERMIT NUMBER 13090414. | | | | 2) NOTES 18 AND 19 ON SHEET M-1, SPECIFY BALANCED AIR | | RETURN, HOWEVER, NO PROVISIONS FOR RETURN AIR IS | | INDICATED AT THE FIRST FLOOR BEDROOMS. PLEASE CLARIFY. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|