2014-06-04 11:34:41 | PLUMBING PLAN REVIEW |
| PERMIT: 14010860 |
| ADD: 2500 METROCENTRE BLVD SUITE # 1 |
| CONT: TO BE DETERMINED |
| TEL: (561)786-486-9513 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: WED. JULY 04/2014 |
| ACTION: PLUMBING PROVISO |
| |
| TOTAL SQ FOOTAGE OF BUILDING 17,973 SQ FT |
| DAYCARE OCCUPANCY 4911 SQ FT APPROX |
| BLDG TYPE 3B |
| |
| 1) DRINKING FOUNTAINS 2 REQUIRED, 2010 FL ACCESS CODE |
| 211.3 MORE THAN MINIMUM NUMBER. |
| WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING |
| FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT |
| OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED |
| SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT |
| OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED |
| SHALL COMPLY WITH 602.7. |
| |
| 602.1 GENERAL.DRINKING FOUNTAINS SHALL COMPLY WITH 307 |
| AND 602. |
| |
| 602.2 CLEAR FLOOR SPACE.UNITS SHALL HAVE A CLEAR FLOOR |
| OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A |
| FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE |
| CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| EXCEPTION: A PARALLEL APPROACH COMPLYING WITH 305 SHALL |
| BE PERMITTED AT UNITS FOR CHILDREN?S USE WHERE THE |
| SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND AND IS 31/2 INCHES (90 MM) MAXIMUM FROM |
| THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS. |
| |
| 602.3 OPERABLE PARTS.OPERABLE PARTS SHALL COMPLY WITH |
| 309. |
| |
| 602.4 SPOUT HEIGHT.SPOUT OUTLETS SHALL BE 36 INCHES |
| (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 602.5 SPOUT LOCATION.THE SPOUT SHALL BE LOCATED 15 |
| INCHES (380 MM) MINIMUM FROM THE VERTICAL SUPPORT AND 5 |
| INCHES (125 MM) MAXIMUM FROM THE FRONT EDGE OF THE |
| UNIT, INCLUDING BUMPERS. |
| |
| 602.6 WATER FLOW.THE SPOUT SHALL PROVIDE A FLOW OF |
| WATER 4 INCHES (100 MM) HIGH MINIMUM AND SHALL BE |
| LOCATED 5 INCHES (125 MM) MAXIMUM FROM THE FRONT OF THE |
| UNIT. THE ANGLE OF THE WATER STREAM SHALL BE MEASURED |
| HORIZONTALLY RELATIVE TO THE FRONT FACE OF THE UNIT. |
| WHERE SPOUTS ARE LOCATED LESS THAN 3 INCHES (75 MM) OF |
| THE FRONT OF THE UNIT, THE ANGLE OF THE WATER STREAM |
| SHALL BE 30 DEGREES MAXIMUM. WHERE SPOUTS ARE LOCATED |
| BETWEEN 3 INCHES (75 MM) AND 5 INCHES (125 MM) MAXIMUM |
| FROM THE FRONT OF THE UNIT, THE ANGLE OF THE WATER |
| STREAM SHALL BE 15 DEGREES MAXIMUM. |
| |
| 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. |
| SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING |
| PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 |
| INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |