Plan Review Notes
Plan Review Notes For Permit 14010860
Permit Number 14010860
Review Stop P
Sequence Number 2
Notes
Date Text
2014-06-04 11:34:41PLUMBING PLAN REVIEW
 PERMIT: 14010860
 ADD: 2500 METROCENTRE BLVD SUITE # 1
 CONT: TO BE DETERMINED
 TEL: (561)786-486-9513
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JULY 04/2014
 ACTION: PLUMBING PROVISO
  
 TOTAL SQ FOOTAGE OF BUILDING 17,973 SQ FT
 DAYCARE OCCUPANCY 4911 SQ FT APPROX
 BLDG TYPE 3B
  
 1) DRINKING FOUNTAINS 2 REQUIRED, 2010 FL ACCESS CODE
 211.3 MORE THAN MINIMUM NUMBER.
 WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING
 FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.7.
  
 602.1 GENERAL.DRINKING FOUNTAINS SHALL COMPLY WITH 307
 AND 602.
  
 602.2 CLEAR FLOOR SPACE.UNITS SHALL HAVE A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 EXCEPTION: A PARALLEL APPROACH COMPLYING WITH 305 SHALL
 BE PERMITTED AT UNITS FOR CHILDREN?S USE WHERE THE
 SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND AND IS 31/2 INCHES (90 MM) MAXIMUM FROM
 THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS.
  
 602.3 OPERABLE PARTS.OPERABLE PARTS SHALL COMPLY WITH
 309.
  
 602.4 SPOUT HEIGHT.SPOUT OUTLETS SHALL BE 36 INCHES
 (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 602.5 SPOUT LOCATION.THE SPOUT SHALL BE LOCATED 15
 INCHES (380 MM) MINIMUM FROM THE VERTICAL SUPPORT AND 5
 INCHES (125 MM) MAXIMUM FROM THE FRONT EDGE OF THE
 UNIT, INCLUDING BUMPERS.
  
 602.6 WATER FLOW.THE SPOUT SHALL PROVIDE A FLOW OF
 WATER 4 INCHES (100 MM) HIGH MINIMUM AND SHALL BE
 LOCATED 5 INCHES (125 MM) MAXIMUM FROM THE FRONT OF THE
 UNIT. THE ANGLE OF THE WATER STREAM SHALL BE MEASURED
 HORIZONTALLY RELATIVE TO THE FRONT FACE OF THE UNIT.
 WHERE SPOUTS ARE LOCATED LESS THAN 3 INCHES (75 MM) OF
 THE FRONT OF THE UNIT, THE ANGLE OF THE WATER STREAM
 SHALL BE 30 DEGREES MAXIMUM. WHERE SPOUTS ARE LOCATED
 BETWEEN 3 INCHES (75 MM) AND 5 INCHES (125 MM) MAXIMUM
 FROM THE FRONT OF THE UNIT, THE ANGLE OF THE WATER
 STREAM SHALL BE 15 DEGREES MAXIMUM.
  
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  