Plan Review Notes
Plan Review Notes For Permit 14010860
Permit Number 14010860
Review Stop P
Sequence Number 1
Notes
Date Text
2014-02-03 18:22:03PLUMBING PLAN REVIEW
 PERMIT: 14010860
 ADD: 2500 METROCENTRE BLVD SUITE # 1
 CONT: TO BE DETERMINED
 TEL: (561)786-486-9513
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY FEB. 03/2014
 ACTION: DENIED
  
 TOTAL SQ FOOTAGE OF BUILDING 17,973 SQ FT
 DAYCARE OCCUPANCY 5,530 SQ FT APPROX
 BLDG TYPE 3B
  
 2010 FBC-B TABLE 1004.1.1
 PROVIDE A BREAK DOWN ON USE AREAS BY SQ FT:
 PRE-SCHOOL
 OPEN SUPPORT
 THEROPY ROOMS
 OFFICES
 STORAGE ROOMS
  
  
 1) PLEAASE PROVIDE THE MINIMUM FIXTURE COUNT REQUIRRED
 BY 2010 FBC-PLUMBING TABLE 403.1
 WATER CLOSETS MALE/ FEMALE
 LAVATORIES MALE/ FEMALE
 DRINKING FOUNTAINS (2) SEE FOOTNOTE (E) THE MINIMUM
 NUMBER OF REQUIRED DRINKING FOUNTAINS SHALL COMPLY WITH
 TABLE 403.1 AND THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
 SERVICE SINK (1) REQUIRED.
  
 2) DRINKING FOUNTAINS 2 REQUIRED, 2010 FL ACCESS CODE
 211.3 MORE THAN MINIMUM NUMBER.
 WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING
 FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.7.
  
 602.1 GENERAL.DRINKING FOUNTAINS SHALL COMPLY WITH 307
 AND 602.
  
 602.2 CLEAR FLOOR SPACE.UNITS SHALL HAVE A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 EXCEPTION: A PARALLEL APPROACH COMPLYING WITH 305 SHALL
 BE PERMITTED AT UNITS FOR CHILDREN?S USE WHERE THE
 SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND AND IS 31/2 INCHES (90 MM) MAXIMUM FROM
 THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS.
  
 602.3 OPERABLE PARTS.OPERABLE PARTS SHALL COMPLY WITH
 309.
  
 602.4 SPOUT HEIGHT.SPOUT OUTLETS SHALL BE 36 INCHES
 (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 602.5 SPOUT LOCATION.THE SPOUT SHALL BE LOCATED 15
 INCHES (380 MM) MINIMUM FROM THE VERTICAL SUPPORT AND 5
 INCHES (125 MM) MAXIMUM FROM THE FRONT EDGE OF THE
 UNIT, INCLUDING BUMPERS.
  
 602.6 WATER FLOW.THE SPOUT SHALL PROVIDE A FLOW OF
 WATER 4 INCHES (100 MM) HIGH MINIMUM AND SHALL BE
 LOCATED 5 INCHES (125 MM) MAXIMUM FROM THE FRONT OF THE
 UNIT. THE ANGLE OF THE WATER STREAM SHALL BE MEASURED
 HORIZONTALLY RELATIVE TO THE FRONT FACE OF THE UNIT.
 WHERE SPOUTS ARE LOCATED LESS THAN 3 INCHES (75 MM) OF
 THE FRONT OF THE UNIT, THE ANGLE OF THE WATER STREAM
 SHALL BE 30 DEGREES MAXIMUM. WHERE SPOUTS ARE LOCATED
 BETWEEN 3 INCHES (75 MM) AND 5 INCHES (125 MM) MAXIMUM
 FROM THE FRONT OF THE UNIT, THE ANGLE OF THE WATER
 STREAM SHALL BE 15 DEGREES MAXIMUM.
  
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
  
  
 3) 606 LAVATORIES AND SINKS
  
 606.1 GENERAL. LAVATORIES AND SINKS SHALL COMPLY WITH
 606.
  
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND
  
 606.4 FAUCETS. CONTROLS FOR FAUCETS SHALL COMPLY WITH
 309. HAND-OPERATED METERING FAUCETS SHALL REMAIN OPEN
 FOR 10 SECONDS MINIMUM.
  
 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY AND
 DRAIN PIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES
 UNDER LAVATORIES AND SINKS.
  
  
 4) SEE 2010 FBC-ACCESSIBILITY CODE FOR 604.9 WATER
 CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S USE.
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE SHALL COMPLY WITH 604.9.
 ADVISORY 604.9 WATER CLOSETS AND TOILET COMPARTMENTS
 FOR CHILDREN?S USE.
 THE REQUIREMENTS IN 604.9 ARE TO BE FOLLOWED WHERE THE
 EXCEPTION FOR CHILDREN?S WATER CLOSETS IN 604.1 IS
 USED. THE FOLLOWING TABLE PROVIDES ADDITIONAL GUIDANCE
 IN APPLYING THE SPECIFICATIONS FOR WATER CLOSETS FOR
 CHILDREN ACCORDING TO THE AGE GROUP SERVED AND REFLECTS
 THE DIFFERENCES IN THE SIZE, STATURE, AND REACH RANGES
 OF CHILDREN AGES 3 THROUGH 12. THE SPECIFICATIONS
 CHOSEN SHOULD CORRESPOND TO THE AGE OF THE PRIMARY USER
 GROUP. THE SPECIFICATIONS OF ONE AGE GROUP SHOULD BE
 APPLIED CONSISTENTLY IN THE INSTALLATION OF A WATER
 CLOSET AND RELATED ELEMENTS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER