Plan Review Notes For Permit 14010860 |
Permit Number |
14010860 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-02-13 10:48:57 | 14010860 | | 2500 METRO CENTER | | CHANGE OF BUSINESS OCCUPANCY TO CHILD DAY CARE. | | | | PROVIDE AN ELECTRICAL AND LIGHTING PLAN. INCLUDE AN | | ELECTRICAL PANEL SCHEDULE SHOWING ALL FEEDERS WITH OVER | | CURRENT PROTECTION AND BRANCH CIRCUITS FOR THE NEW | | OCCUPANCY. NEC 215.5 | | | | SHOW LOCATION OF PANEL BOARDS. PROVIDE A DEDICATED SAFE | | WORKING SPACE FOR THE ELECTRICAL PANEL BOARDS. NEC | | 110.26 | | | | SHOW THE EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK | | UP. FBC 1011 | | | | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS AND | | WITHIN BATHROOMS AND OUTDOORS MUST BE GFCI PROTECTED. | | NEC 210.8 | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | ELECTRIC DRINKING FOUNTAINS MUST BE GFCI PROTECTED. NEC | | 422.52 | | | | ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.12 | | | | A FIRE DETECTION AND ALARM SYSTEM IS REQUIRED. FBC | | 436.7 | | | | A SEPARATE CIRCUIT IS REQUIRED FOR THE FIRE ALARM | | SYSTEM. NEC 760.41 | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | SYSTEMS, SECURITY AND DATA SYSTEMS. | | | | ROBERT LECKY, CBO | | ELECTRICAL PLANS REVIEW | | 561-373-3701 | | |
|