2014-02-03 18:01:03 | BUILDING PLAN REVIEW |
| PERMIT: 14010860 |
| ADD: 2500 METROCENTRE BLVD SUITE # 1 |
| CONT: TO BE DETERMINED |
| TEL: (561)786-486-9513 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MONDAY FEB. 03/2014 |
| ACTION: DENIED |
| |
| TOTAL SQ FOOTAGE OF BUILDING 17,973 SQ FT |
| DAYCARE OCCUPANCY 5,530 SQ FT APPROX |
| BLDG TYPE 3B |
| |
| PROVIDE A BREAK DOWN ON USE AREAS BY SQ FT: |
| PRE-SCHOOL |
| OPEN SUPPORT |
| THEROPY ROOMS |
| OFFICES |
| STORAGE ROOMS |
| |
| CHANGE OF OCCUPANCY: BUSINESS TO DAYCARE/ 2010 EXISTING |
| BUILDING CODE CHAPTER 9 : 901.3.1 PARTIAL CHANGE OF |
| OCCUPANCY CLASSIFICATION. WHERE A PORTION OF AN |
| EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY |
| CLASSIFICATION, SECTION 912 SHALL APPLY. |
| |
| 1) WITH THIS TENANT SPACE BEING A CHANGE OF OCCUPANCY |
| FROM BUSINESS TO DACARE OCCUPANCY THE DESIGNER OF |
| RECORD WILL NEED TO COMPLY WITH 912.1.1 COMPLIANCE WITH |
| CHAPTER 8. THE REQUIREMENTS OF CHAPTER 8 SHALL BE |
| APPLICABLE THROUGHOUT THE BUILDING FOR THE NEW |
| OCCUPANCY CLASSIFICATION BASED ON THE SEPARATION |
| CONDITIONS SET FORTH IN SECTIONS 912.1.1.1 AND |
| 912.1.1.2. |
| |
| 912.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT |
| SEPARATION. |
| WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A |
| NEW OCCUPANCY CLASSIFICATION AND THAT PORTION IS NOT |
| SEPARATED FROM THE REMAINDER OF THE BUILDING WITH A |
| FIRE-RATED WALL/CEILING HAVING A FIRE-RESISTANCE RATING |
| AS REQUIRED IN THE FLORIDA BUILDING CODE, BUILDING FOR |
| THE SEPARATE OCCUPANCY, THE ENTIRE BUILDING SHALL |
| COMPLY WITH ALL OF THE REQUIREMENTS OF CHAPTER 8 |
| APPLIED THROUGHOUT THE BUILDING FOR THE MOST |
| RESTRICTIVE OCCUPANCY CLASSIFICATION IN THE BUILDING |
| AND WITH THE REQUIREMENTS OF THIS CHAPTER. |
| |
| 912.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH |
| SEPARATION. REQUIRES A (2) HR OCCUPANCY SEPERATION. |
| WHERE A PORTION OF AN EXISTING BUILDING THAT IS CHANGED |
| TO A NEW OCCUPANCY CLASSIFICATION AND THAT PORTION IS |
| SEPARATED FROM THE REMAINDER OF THE BUILDING WITH FIRE |
| BARRIERS HAVING A FIRE-RESISTANCE RATING AS REQUIRED IN |
| THE FLORIDA BUILDING CODE, BUILDING FOR THE SEPARATE |
| OCCUPANCY, THAT PORTION SHALL COMPLY WITH ALL THE |
| REQUIREMENTS OF CHAPTER 8 FOR THE NEW OCCUPANCY |
| CLASSIFICATION AND WITH THE REQUIREMENTS OF THIS |
| CHAPTER. |
| |
| 2) 912.1.2 FIRE PROTECTION AND INTERIOR FINISH. THE |
| PROVISIONS OF SECTIONS 912.2 AND 912.3 FOR FIRE |
| PROTECTION AND INTERIOR FINISH, RESPECTIVELY, SHALL |
| APPLY TO ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| CLASSIFICATION. |
| 912.3 INTERIOR FINISH. IN AREAS OF THE BUILDING |
| UNDERGOING THE CHANGE OF OCCUPANCY CLASSIFICATION, THE |
| INTERIOR FINISH OF WALLS AND CEILINGS SHALL COMPLY WITH |
| THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING |
| FOR THE NEW OCCUPANCY CLASSIFICATION. |
| SEE 2010 FBC-B TABLE 803.9 INTERIOR WALL & CEILING |
| FINISHE REQUIREMENTS BY OCCUPANCY/ DAYCARE- |
| NONSPRINKLERED. |
| |
| 3) 912.1.4 ACCESSIBILITY. |
| ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH SECTION 912.8. 912.8 |
| ACCESSIBILITY. EXISTING BUILDINGS THAT UNDERGO A CHANGE |
| OF GROUP OR OCCUPANCY CLASSIFICATION SHALL COMPLY WITH |
| THE PROVISIONS OF THE FLORIDA BUILDING CODE, |
| ACCESSIBILITY. |
| |
| 2010 FLBC- ACCESSIBILITY CODE 202.4.1 DISPROPORTIONATE |
| COST. |
| ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| |
| 2010 FLBC- ACCESSIBILITY CODE 202.4.2 ACCESSIBLE |
| FEATURES IN THE EVENT OF DISPROPORTIONALITY. |
| WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| ALARMS. |
| |
| 4) 912.2 FIRE PROTECTION SYSTEMS. FIRE PROTECTION |
| SYSTEMS SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS |
| 912.2.1 AND 912.2.2 |
| 912.2.1 NOT REQUIRED- FIRE SPRINKLERS |
| |
| 912.2.2 FIRE ALARM AND DETECTION SYSTEM. |
| WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE |
| PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED. |
| 436.7.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM |
| SHALL BE BY MANUAL MEANS AND BY OPERATION OF ANY |
| REQUIRED SMOKE DETECTORS AND REQUIRED SPRINKLER |
| SYSTEMS. |
| |
| 436.7.1.1 OCCUPANT NOTIFICATION SIGNALS SHALL BE |
| AUDIBLE AND VISUAL SIGNALS IN ACCORDANCE WITH NFPA 72 |
| AND THE FLORIDA BUILDING CODE, ACCESSIBILITY. THE |
| GENERAL EVACUATION ALARM SIGNAL SHALL OPERATE |
| THROUGHOUT THE ENTIRE BUILDING. |
| EXCEPTIONS: 1. WHERE TOTAL EVACUATION OF OCCUPANTS IS |
| IMPRACTICAL BECAUSE OF BUILDING CONFIGURATION, ONLY THE |
| OCCUPANTS IN THE AFFECTED ZONES SHALL BE INITIALLY |
| NOTIFIED. PROVISIONS SHALL BE MADE TO SELECTIVELY |
| NOTIFY OCCUPANTS IN OTHER ZONES TO AFFORD ORDERLY |
| EVACUATION OF THE ENTIRE BUILDING. |
| 2. WHERE OCCUPANTS ARE INCAPABLE OF EVACUATING |
| THEMSELVES BECAUSE OF AGE, PHYSICAL OR MENTAL |
| DISABILITY OR PHYSICAL RESTRAINT, THE PRIVATE OPERATING |
| MODE AS DESCRIBED IN NFPA 72 SHALL BE PERMITTED TO BE |
| USED. ONLY THE ATTENDANTS AND OTHER PERSONNEL REQUIRED |
| TO EVACUATE OCCUPANTS FROM A ZONE, AREA, FLOOR, OR |
| BUILDING SHALL BE REQUIRED TO BE NOTIFIED. THIS |
| NOTIFICATION SHALL INCLUDE MEANS TO READILY IDENTIFY |
| THE ZONE, AREA, FLOOR OR BUILDING IN NEED OF |
| EVACUATION. |
| |
| 436.7.1.2 FIRE DEPARTMENT NOTIFICATION. |
| THE FIRE ALARM SYSTEM SHALL BE ARRANGED TO TRANSMIT THE |
| ALARM AUTOMATICALLY TO THE FIRE DEPARTMENT IN |
| ACCORDANCE WITH NFPA 72 BY MEANS OF ONE OF THE |
| FOLLOWING METHODS AS APPROVED BY THE BUILDING OFFICIAL: |
| 1. AN AUXILIARY ALARM SYSTEM, OR |
| 2. A CENTRAL STATION CONNECTION, OR |
| 3. A PROPRIETARY SYSTEM, OR |
| 4. A REMOTE STATION CONNECTION. |
| EXCEPTION: WHERE NONE OF THE ABOVE MEANS OF |
| NOTIFICATION IS AVAILABLE, A PLAN FOR NOTIFICATION OF |
| THE FIRE DEPARTMENT, ACCEPTABLE TO THE BUILDING |
| OFFICIAL, SHALL BE PROVIDED. |
| |
| 436.7.2 DETECTION. |
| A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN |
| ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN |
| EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN |
| THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE |
| OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN |
| LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY |
| CARE OCCUPANCY. |
| EXCEPTION: DAY CARE OCCUPANCIES HOUSED IN ONE ROOM. |
| |
| 5) 912.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD |
| CATEGORY. WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS |
| MADE TO A HIGHER HAZARD CATEGORY (LOWER NUMBER) AS |
| SHOWN IN TABLE 912.4, THE MEANS OF EGRESS SHALL COMPLY |
| WITH THE REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| 2010 FBC-B 1029.4.1 |
| EVERY ROOM OR SPACE GREATER THAN 250 SQUARE FEET (23.2 |
| M2) IN EDUCATIONAL OCCUPANCIES USED FOR |
| CLASSROOM OR OTHER EDUCATIONAL PURPOSES OR NORMALLY |
| SUBJECT TO STUDENT OCCUPANCY AND EVERY ROOM |
| OR SPACE NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER |
| THAN BATHROOMS, IN GROUP D OCCUPANCIES SHALL |
| HAVE NOT LESS THAN ONE OUTSIDE WINDOW FOR EMERGENCY |
| RESCUE THAT COMPLIES WITH THE FOLLOWING: |
| 1.SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR |
| OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH, |
| 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE |
| FEET (0.53 M2) IN AREA. |
| 2.THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 |
| INCHES (1118 MM) ABOVE THE FLOOR, AND ANY |
| LATCHING DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM |
| NOT MORE THAN 54 INCHES (1372 MM) ABOVE |
| THE FINISHED FLOOR. |
| EXCEPTIONS: |
| 1.BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH SECTION 903.3.1.1. |
| 2.WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY |
| TO THE OUTSIDE OF THE BUILDING. |
| |
| 6) 436.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL BE |
| SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE |
| CLOSET. |
| |
| 7) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK SHALL |
| BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR FROM |
| THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE SHALL |
| BE READILY ACCESSIBLE TO THE STAFF. |
| |
| 6) 436.6 PROTECTION FROM HAZARDS. |
| ROOMS OR SPACES FOR THE STORAGE, PROCESSING OR USE OF |
| MATERIALS SPECIFIED BELOW SHALL BE PROTECTED IN |
| ACCORDANCE WITH THE FOLLOWING: |
| |
| 6A) 436.6.1 |
| THE FOLLOWING ROOMS OR SPACES SHALL BE SEPARATED FROM |
| THE REMAINDER OF THE BUILDING BY FIRE BARRIERS HAVING A |
| FIRE RESISTANCE RATING OF NOT LESS THAN 1-HOUR OR SHALL |
| BE PROTECTED BY AN APPROVED AUTOMATIC EXTINGUISHING |
| SYSTEM. |
| |
| 1. BOILER AND FURNACE ROOMS. |
| |
| EXCEPTION: ROOMS ENCLOSING ONLY AIR-HANDLING EQUIPMENT. |
| |
| 2. ROOMS OR SPACES USED FOR THE STORAGE OF COMBUSTIBLE |
| SUPPLIES IN QUANTITIES DEEMED HAZARDOUS BY THE BUILDING |
| OFFICIAL. |
| |
| 3. ROOMS OR SPACES USED FOR THE STORAGE OF HAZARDOUS |
| MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS IN |
| QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS. |
| |
| 4. JANITOR CLOSETS. |
| |
| EXCEPTION: DOORS TO JANITOR CLOSETS SHALL BE PERMITTED |
| TO HAVE VENTILATING LOUVERS WHERE THE SPACE IS |
| PROTECTED BY AUTOMATIC SPRINKLERS. |
| |
| 6B) 436.6.2 |
| THE FOLLOWING ROOMS OR SPACES SHALL BE SEPARATED FROM |
| THE REMAINDER OF THE BUILDING BY FIRE BARRIERS HAVING A |
| FIRE RESISTANCE RATING OF NOT LESS THAN 1 HOUR AND |
| SHALL BE PROTECTED BY AN APPROVED AUTOMATIC |
| FIRE-EXTINGUISHING SYSTEM. |
| |
| 1. LAUNDRIES. |
| |
| 2. MAINTENANCE SHOPS, INCLUDING WOODWORKING AND |
| PAINTING AREAS. |
| |
| 3. ROOMS OR SPACES USED FOR PROCESSING OR USE OF |
| COMBUSTIBLE SUPPLIES DEEMED HAZARDOUS BY THE BUILDING |
| OFFICIAL. |
| |
| 4. ROOMS OR SPACES USED FOR PROCESSING OR USE OF |
| HAZARDOUS MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS |
| IN QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS. |
| |
| EXCEPTION: FOOD PREPARATION FACILITIES PROTECTED IN |
| ACCORDANCE WITH NFPA 96 SHALL NOT BE REQUIRED TO HAVE |
| OPENINGS PROTECTED BETWEEN FOOD PREPARATION AREAS AND |
| DINING AREAS. WHERE DOMESTIC COOKING EQUIPMENT IS USED |
| FOR FOOD WARMING OR LIMITED COOKING, PROTECTION OR |
| SEGREGATION OF FOOD PREPARATION FACILITIES SHALL NOT BE |
| REQUIRED IF APPROVED BY THE BUILDING OFFICIAL. |
| |
| 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |