Plan Review Notes For Permit 14010763 |
Permit Number |
14010763 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-01-22 12:24:55 | MECHANICAL PLAN REVIEW | | PERMIT: 14010763 | | ADD: 1781 PALM BEACH LAKES SUITE # W233 | | CONT: TO BE DETREMINED | | TEL: (561 | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | DATE: WEDNESDAY JAN. 22/ 2014 | | ACTION: PROVISO | | | | 1) 2010 FBC-M 606.2.2 COMMON SUPPLY, RETURN AIR AND | | SUPPLY AIR SYSTEMS. | | WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY | | OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN | | CAPACITY GREATER THAN 2,000 CFM (0.9 M3/S), THE RETURN | | AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH SMOKE | | DETECTORS IN ACCORDANCE WITH SECTION 606.2.1. 606.2.1 | | SUPPLY AIR SYSTEMS. SMOKE DETECTORS SHALL BE INSTALLED | | IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY GREATER | | THAN 2,000 CFM (0.9 M3/S) IN THE SUPPLY AIR DUCT. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|