Plan Review Notes
Plan Review Notes For Permit 14010763
Permit Number 14010763
Review Stop M
Sequence Number 1
Notes
Date Text
2014-01-22 12:24:55MECHANICAL PLAN REVIEW
 PERMIT: 14010763
 ADD: 1781 PALM BEACH LAKES SUITE # W233
 CONT: TO BE DETREMINED
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 1ST REVIEW
 DATE: WEDNESDAY JAN. 22/ 2014
 ACTION: PROVISO
  
 1) 2010 FBC-M 606.2.2 COMMON SUPPLY, RETURN AIR AND
 SUPPLY AIR SYSTEMS.
 WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY
 OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN
 CAPACITY GREATER THAN 2,000 CFM (0.9 M3/S), THE RETURN
 AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH SMOKE
 DETECTORS IN ACCORDANCE WITH SECTION 606.2.1. 606.2.1
 SUPPLY AIR SYSTEMS. SMOKE DETECTORS SHALL BE INSTALLED
 IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY GREATER
 THAN 2,000 CFM (0.9 M3/S) IN THE SUPPLY AIR DUCT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER