Plan Review Notes
Plan Review Notes For Permit 14010763
Permit Number 14010763
Review Stop B
Sequence Number 1
Notes
Date Text
2014-01-22 12:07:15BUILDING PLAN REVIEW
 PERMIT: 14010763
 ADD: 1781 PALM BEACH LAKES SUITE # W233
 CONT: TO BE DETREMINED
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 1ST REVIEW
 DATE: WEDNESDAY JAN. 22/ 2014
 ACTION: DENIED
  
  
 1) THE PERMIT APPLICATION WILL NEED TO BE UPDATED,
 UNDER THE DESCRIPTION OF WORK, ADDING STOCKROOM WALLS &
 LIGHTING. PLEASE NOTE THIS SPACE IS A SHELL ONLY SPACE,
 THERE HAS NEVER BEEN A TENANT TO RECEIVE A CERTIFICATE
 OF OCCUPANCY. THIS IS A TENANT BUILD-OUT THAT WILL
 RECIEVE A CERTIFICATE OF OCCUPANCY.
  
 2) FOR THIS TENANT BUILD-OUT PLEASE SEE PB OUTLET MALL
 REQUIREMENT IF THE SHELL CONTRACTOR HAS NOT RECIEVED A
 CERTIFICATE OF COMPLETION.
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 3) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN;
 107.3.5.1 COMMERCIAL BUILDINGS:
 3A) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3B) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 3C) LIFE SAFETY PLAN OCCUPANCY LOAD/EGRESS REQUIREMENTS
 SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS, HOW MANY EXITS ARE REQUIRED.
 EXIT
 EMERGENCY LIGHTING AND EXIT SIGNS
 FLOOR PLAN WITH AISLES BETWEEN SALES COUNTERS,
 MERCHANDISE STANDS, KIOSK AND CASH WRAP
 3D) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 ACCESSIBLE ROUTE
 DRESSING ROOMS FL ACC CODE 803.1-5
 CASH WRAPS FL ACC CODE 904.1- 4.2
 3E) INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION,
  
 4) SHEET LS01 INDICATES THE OCCUPANCY LOAD OF 209
 OCCUPANTS AND A SECOND MEANS OF EGRESS THROUGH THE
 STOCKROOM. PLEASE PROVIDE COMPLIANCE WITH THE
 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
  
 1.EXCEPTION: MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 ADJOINING OR INTERVENING ROOMS OR SPACES IN A GROUP H,
 S OR F OCCUPANCY WHEN THE ADJOINING OR INTERVENING
 ROOMS OR SPACES ARE THE SAME OR A LESSER HAZARD
 OCCUPANCY GROUP.
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
  
 EXCEPTIONS:
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA
 TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 5) THE VALUE APPEARS TO BE LOW FOR THE AMOUNT OF WORK
 THAT WILL BE COMPLETED UNDER THIS PERMIT. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 2010 EDITION W P B
 ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON
 BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND
 PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A
 FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  