Plan Review Notes For Permit 14010762 |
Permit Number |
14010762 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-01-22 13:08:23 | PLUMBING PLAN REVIEW | | PERMIT: 14010762 | | ADD: 1793 PALM BEACH LAKES SUITE # W404 | | CONT: TO BE DETREMINED | | TEL: (561 | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | DATE: WEDNESDAY JAN. 22/ 2014 | | ACTION: DENIED | | | | 1) SHEET LS.01 LIFE SAFETY SHEET INDICATES A MERCANTILE | | OCCUPANCY WITH A FOOTPRINT OF 3262 SQ FT & OCCUPANT | | LOAD OF 85. THE 2010 FBC-PLUMBING CODE TABLE 403.1 DOES | | REQUIRE 2 TOLIET FACILITIES, THIS TENANT SPACE IS CLOSE | | ENOUGH TO THE GANGED RESTROOMS IN J1 AND J2 TO FIGURE | | FOR ONE TOLIET SPACE. THE FBC-PLUMBING CODE SECTION | | 403.3.1 ACCESS. THE ROUTE TO THE PUBLIC TOILET | | FACILITIES REQUIRED BY SECTION 403.3 SHALL NOT PASS | | THROUGH KITCHENS, STORAGE ROOMS OR CLOSETS. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | |
|