2014-01-22 13:13:01MECHANICAL PLAN REVIEW
 PERMIT: 14010762
 ADD: 1793 PALM BEACH LAKES SUITE # W404
 CONT: TO BE DETREMINED
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 1ST REVIEW
 DATE: WEDNESDAY JAN. 22/ 2014
 ACTION: PROVISO
  
 1) 2010 FBC-M 606.2.1.
 . 606.2.1 SUPPLY AIR SYSTEMS. SMOKE DETECTORS SHALL BE
 INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM (0.9 M3/S) IN THE SUPPLY AIR
 DUCT.
  