Date |
Text |
2014-01-22 13:00:54 | BUILDING PLAN REVIEW |
| PERMIT: 14010762 |
| ADD: 1793 PALM BEACH LAKES SUITE # W404 |
| CONT: TO BE DETREMINED |
| TEL: (561 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| |
| 1ST REVIEW |
| DATE: WEDNESDAY JAN. 22/ 2014 |
| ACTION: DENIED |
| |
| |
| 1) THE PERMIT APPLICATION WILL NEED TO BE UPDATED, |
| UNDER THE DESCRIPTION OF WORK, ADDING STOCKROOM WALLS. |
| PLEASE NOTE THIS SPACE IS A SHELL ONLY SPACE, THERE HAS |
| NEVER BEEN A TENANT TO RECEIVE A CERTIFICATE OF |
| OCCUPANCY. THIS IS A TENANT BUILD-OUT THAT WILL RECIEVE |
| A CERTIFICATE OF OCCUPANCY. |
| |
| 2) FOR THIS TENANT BUILD-OUT PLEASE SEE PB OUTLET MALL |
| REQUIREMENT IF THE SHELL CONTRACTOR HAS NOT RECIEVED A |
| CERTIFICATE OF COMPLETION. |
| A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT |
| CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND |
| NOTARIZED. |
| |
| 3) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY THE |
| BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM |
| CRITERIA AND DOCUMENTS: A FLOOR PLAN; |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 3A) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| 3B) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). |
| 3C) LIFE SAFETY PLAN OCCUPANCY LOAD/EGRESS REQUIREMENTS |
| SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS, HOW MANY EXITS ARE REQUIRED. |
| EXIT |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| FLOOR PLAN WITH AISLES BETWEEN SALES COUNTERS, |
| MERCHANDISE STANDS, KIOSK AND CASH WRAP |
| 3D) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| FOLLOWING: |
| ACCESSIBLE ROUTE |
| DRESSING ROOMS FL ACC CODE 803.1-5 |
| CASH WRAPS FL ACC CODE 904.1- 4.2 |
| 3E) INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| LIGHT AND VENTILATION, |
| |
| 4) SHEET LS01 INDICATES THE OCCUPANCY LOAD OF 85 |
| OCCUPANTS AND A SECOND MEANS OF EGRESS THROUGH THE |
| STOCKROOM. PLEASE PROVIDE COMPLIANCE WITH THE |
| 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES. |
| EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH |
| THIS SECTION. |
| |
| 1.EXCEPTION: MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| ADJOINING OR INTERVENING ROOMS OR SPACES IN A GROUP H, |
| S OR F OCCUPANCY WHEN THE ADJOINING OR INTERVENING |
| ROOMS OR SPACES ARE THE SAME OR A LESSER HAZARD |
| OCCUPANCY GROUP. |
| 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| |
| EXCEPTIONS: |
| 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE |
| FOLLOWING ARE MET: |
| |
| 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| THAT FOUND IN THE MAIN RETAIL AREA; |
| |
| 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| THROUGH THE STOCKROOM; |
| |
| 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| EGRESS SIDE; AND |
| |
| 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| TO THE EXIT WITHOUT OBSTRUCTIONS. |
| |
| 5) THE VALUE APPEARS TO BE LOW FOR THE AMOUNT OF WORK |
| THAT WILL BE COMPLETED UNDER THIS PERMIT. 2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION, 2010 EDITION W P B |
| ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON |
| BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND |
| PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A |
| FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |