Date |
Text |
2014-01-22 18:12:06 | |
| 1) VALUE IS LOW FOR THE AMOUNT OF WORK TO BE COMPLETED |
| UNDER THE SCOPE OF THIS PERMIT. HOLD WILL BE PUT OM |
| PERMIT UNTILS FEES ARE INCREASED. |
| |
| W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) EGRESS PATHS CAN NOT BE CHECKED ON PLANS WILL BE |
| REVIEWED COMPLIANCE WITH 2010 FBC-B 1017.3 AISLE |
| ACCESSWAYS IN MERCANTILE OCCUPANCIES. |
| |
| 3) PLANS DO NOT SHOW ACCESSIBLE AISLES 2010 FL |
| ACCESSIBILITY CODE 403.5.1. |
| |
| 4) PLANS DO NOT PROVIDE ENOUGH INFORMATION AS TO IF |
| EITHER TENANT SPACE WILL REQUIRE DRESSING ROOMS, IF IF |
| SO THEN COMPLIANCE WITH 2010 FL ACCESSIBILITY CODE |
| 903.4.1-5. |
| |
| 5) PLANS ALSO FAIL TO PROVIDE COMPLIANCE WITH 2010 FL |
| ACCESSIBILITY CODE 904.3.2 ,904.4.1-2. |
| |
| 6) THE BASE BUILDING (SHELL) PERMIT # 12100555 NOR DOES |
| THE LATEST REVISION # 13120864 TO THE SHELL PERMIT EVEN |
| SHOW A TENANT SPACE E244, THIS IS A NEW TENANT |
| SEPERATION WALL. PLANS SHOW THE WALL TO BE A ONE HOUR |
| FIRE RATING, PLEASE PROVIDE A DETAIL FOR THE 1 HOUR |
| FIRE RATED WALL, PLEASE PROVIDE COMPLIANCE WITH |
| 2010 FBC-B 709.4 CONTINUITY AND EITHER PROVIDE THE UL |
| LISTING OR GYPSUM ASSOCIATION LISTING. |
| |