Plan Review Notes
Plan Review Notes For Permit 14010760
Permit Number 14010760
Review Stop B
Sequence Number 1
Notes
Date Text
2014-01-22 18:12:06 
 1) VALUE IS LOW FOR THE AMOUNT OF WORK TO BE COMPLETED
 UNDER THE SCOPE OF THIS PERMIT. HOLD WILL BE PUT OM
 PERMIT UNTILS FEES ARE INCREASED.
  
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) EGRESS PATHS CAN NOT BE CHECKED ON PLANS WILL BE
 REVIEWED COMPLIANCE WITH 2010 FBC-B 1017.3 AISLE
 ACCESSWAYS IN MERCANTILE OCCUPANCIES.
  
 3) PLANS DO NOT SHOW ACCESSIBLE AISLES 2010 FL
 ACCESSIBILITY CODE 403.5.1.
  
 4) PLANS DO NOT PROVIDE ENOUGH INFORMATION AS TO IF
 EITHER TENANT SPACE WILL REQUIRE DRESSING ROOMS, IF IF
 SO THEN COMPLIANCE WITH 2010 FL ACCESSIBILITY CODE
 903.4.1-5.
  
 5) PLANS ALSO FAIL TO PROVIDE COMPLIANCE WITH 2010 FL
 ACCESSIBILITY CODE 904.3.2 ,904.4.1-2.
  
 6) THE BASE BUILDING (SHELL) PERMIT # 12100555 NOR DOES
 THE LATEST REVISION # 13120864 TO THE SHELL PERMIT EVEN
 SHOW A TENANT SPACE E244, THIS IS A NEW TENANT
 SEPERATION WALL. PLANS SHOW THE WALL TO BE A ONE HOUR
 FIRE RATING, PLEASE PROVIDE A DETAIL FOR THE 1 HOUR
 FIRE RATED WALL, PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-B 709.4 CONTINUITY AND EITHER PROVIDE THE UL
 LISTING OR GYPSUM ASSOCIATION LISTING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]