Plan Review Notes
Plan Review Notes For Permit 14010620
Permit Number 14010620
Review Stop P
Sequence Number 1
Notes
Date Text
2014-03-03 11:06:24NO PLUMBING WORK IS SPECIFIED AS PART OF THIS PERMIT. A
 SEPARATE APPLICATION, PERMIT AND REVIEW IS REQUIRED FOR
 PLUMBING WORK.2010 FBC
  
 DENIED BY PLUMBING
  
 1) THE BATHROOM FIXTURES ARE NOT PROPERLY VENTED. THERE
 ARE TWO WET-VENTED FIXTURE DRAINS DISCHARGING UPSTREAM
 OF THE DRY-VENTED FIXTURE DRAIN CONNECTION. THIS IS NOT
 ALLOWED BY CODE. SEE FBCR P3108.2.1
  
 2) THE PLUMBING RISER DIAGRAM DOES NOT MATCH THE FLOOR
 PLAN. THE DRAINS FOR THE CLOTHES WASHER AND THE KITCHEN
 SINK ARE NOT SHOWN. CITY AMENDMENTS 107.2.1 AND
 107.3.5.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]