1 |
|
Notes |
Date |
Text |
2014-03-03 11:06:24 | NO PLUMBING WORK IS SPECIFIED AS PART OF THIS PERMIT. A | | SEPARATE APPLICATION, PERMIT AND REVIEW IS REQUIRED FOR | | PLUMBING WORK.2010 FBC | | | | DENIED BY PLUMBING | | | | 1) THE BATHROOM FIXTURES ARE NOT PROPERLY VENTED. THERE | | ARE TWO WET-VENTED FIXTURE DRAINS DISCHARGING UPSTREAM | | OF THE DRY-VENTED FIXTURE DRAIN CONNECTION. THIS IS NOT | | ALLOWED BY CODE. SEE FBCR P3108.2.1 | | | | 2) THE PLUMBING RISER DIAGRAM DOES NOT MATCH THE FLOOR | | PLAN. THE DRAINS FOR THE CLOTHES WASHER AND THE KITCHEN | | SINK ARE NOT SHOWN. CITY AMENDMENTS 107.2.1 AND | | 107.3.5.3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|