Plan Review Notes For Permit 14010620 |
Permit Number |
14010620 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-03-03 13:59:37 | NO MECHANICAL WORK IS SPECIFIED AS PART OF THIS PERMIT. | | A SEPARATE APPLICATION, PERMIT AND REVIEW IS REQUIRED | | FOR MECHANICAL WORK. | | | | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS FOR | | THE HEATING/COOLING EQUIPMENT. FBCR M1401.3 | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL | | PLANS THAT MATCHES THE SIZING CALCULATIONS. CITY | | AMENDMENTS 107.3.5.3 | | | | 3) SPECIFY THE DUCT LOCATION AND SIZES, THE GRILL SIZES | | AND CFMS AT EACH SUPPLY OUTLET, SHOW LOCATION AND SIZE | | OF RETURN DUCTS AND GRILLS. CITY AMENDMENTS 107.3.5.3 | | | | 4) SHOW THE LOCATION OF THE HVAC EQUIPMENT ON THE | | PLANS. CITY AMENDMENTS 107.3.5.3 | | | | 5) SHOW THE A/C DISCONNECTS AND EQUIPMENT SERVICING | | RECEPTACLE OUTLET ON THE PLANS. NEC 422.31 AND 210.63 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|