2014-01-10 17:14:552010 FBC
  
 DENIED BY BUILDING
  
 1) THIS STRUCTURE IS LOCATED IN 170 MPH VULT WIND SPEED
 EXPOSURE C THE UPLIFT FOR THE FLAT ROOF EXCEEDS THE
 MAXIMUM DESIGN PRESSURE OF THE -60 PSF SPECIFIED ON
 PAGE 22 OF NOA NO.13-0514.10 . SUBMIT TWO SETS OF
 SIGNED AND SEALED RAS117 CALCULATIONS FOR ENHANCED
 FASTENING AT THE PERIMETER AND CORNER ROOF AREAS AS
 REQUIRED BY LIMITATION NUMBER 7 ON PAGE 26 OF THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714