2014-01-11 10:21:08 | 2010 FBC AND 2008 NEC | | | | DENIED BY ELECTRIC - AN ELECTRICAL PERMIT IS REQUIRED. | | | | 1) SPECIFY THE SCOPE OF ELECTRICAL WORK ON THE PLANS. | | 2) THE NEW BATHROOM IS REQUIRED TO HAVE AT LEAST ONE | | GFCI PROTECTED RECEPTACLE OUTLET INSTALLED WITHIN THREE | | FEET OF THE LAVATORY BASIN. NEC 210.52 (D) AND NEC | | 210.8 | | 3) THE NEW BATHROOM IS REQUIRED TO HAVE AT LEAST ONE | | WALL SWITCH-CONTROLLED LIGHTING OUTLET PER NEC 210.70 | | (A) (1) | | 4) THE NEW BATHROOM EXHAUST FAN WILL REQUIRE ELECTRICAL | | WORK. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|