Plan Review Notes
Plan Review Notes For Permit 14010556
Permit Number 14010556
Review Stop E
Sequence Number 1
Notes
Date Text
2014-01-11 10:21:082010 FBC AND 2008 NEC
  
 DENIED BY ELECTRIC - AN ELECTRICAL PERMIT IS REQUIRED.
  
 1) SPECIFY THE SCOPE OF ELECTRICAL WORK ON THE PLANS.
 2) THE NEW BATHROOM IS REQUIRED TO HAVE AT LEAST ONE
 GFCI PROTECTED RECEPTACLE OUTLET INSTALLED WITHIN THREE
 FEET OF THE LAVATORY BASIN. NEC 210.52 (D) AND NEC
 210.8
 3) THE NEW BATHROOM IS REQUIRED TO HAVE AT LEAST ONE
 WALL SWITCH-CONTROLLED LIGHTING OUTLET PER NEC 210.70
 (A) (1)
 4) THE NEW BATHROOM EXHAUST FAN WILL REQUIRE ELECTRICAL
 WORK.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]