Plan Review Notes
Plan Review Notes For Permit 14010556
Permit Number 14010556
Review Stop B
Sequence Number 1
Notes
Date Text
2014-01-11 08:21:562010 FBC
  
 DENIED BY BUILDING
  
 1) THE SCOPE OF WORK FOR THIS PROJECT IS TO CONVERT AN
 EXISTING CLOSET INTO A FULL BATHROOM. (SEE PLUMBING
 PERMIT #13110189)
  
 2) BECAUSE THERE IS NO OPENABLE WINDOW IN THE PROPOSED
 BATHROOM, MECHANICAL VENTILATION IS REQUIRED BY FBC
 R303.3. THE MINIMUM VENTILATION RATE IS 50 CFM FOR
 INTERMITTENT VENTILATION AND THE AIR IS REQUIRED TO BE
 EXHAUSTED DIRECTLY TO THE OUTSIDE.
  
 3) SPECIFY THE DIMENSIONS OF THE SHOWER ON THE PLANS
 AND SHOW COMPLIANCE WITH THE CLEAR SPACE REQUIRED FOR
 THE LAVATORY, WATER CLOSET AND SHOWER FIXTURES SEE FBC
 R307.1 AND FIGURE R307.1
  
 4) SHOW COMPLIANCE WITH FBCR 314.3.1 WHICH REQUIRES
 SMOKE ALARMS TO BE INSTALLED WHEN ALTERATIONS REQUIRING
 A PERMIT OCCUR.
  
 5) THE PLANS THAT WERE SUBMITTED FOR THE PLUMBING ON
 THIS PROJECT DO NOT MATCH THESE PLANS. THE LOCATION OF
 THE WATER CLOSET AND THE LAVATORY ARE REVERSED. THE
 LOCATION OF THE ROOM ON THE FLOOR PLAN IS ALSO
 DIFFERENT. PLEASE INDICATE WHICH IS THE CORRECT ONE.
 CITY AMENDMENTS 107..2.1
  
 6) PLEASE INDICATE IF THIS PERMIT WILL BE THE MASTER
 FOR THIS PROJECT AND THE PLUMBING AND OTHER TRADES WILL
 BE SUB-PERMITS. IF THIS IS THE CASE REVISE THE VALUE OF
 WORK FOR THIS PERMIT TO INCLUDE ALL OF THE WORK THAT
 WILL BE DONE ON THE APPLICATION. THE VALUE FOR THE WORK
 ON THE SUB-PERMITS WILL BE ZERO BECAUSE THE VALUE WILL
 BE INCLUDED IN THE MASTER.
  
 7) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW THESE
 ITEMS HAVE BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved