 PLUMBING PLAN REVIEW
 PERMIT: 14010549
 ADD: 701 NEW JERSEY ST
 CONT:DON LIPSCOMS PLUMBING
 TEL: (561)310-9245
  
 2010 FLORIDA PLUMBING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 14/2014
 ACTION: DENIED
  
 1) PROVIDE THE MANUFACTURERS SPEC SHEETS, IF MORE THAN
 ONE MODEL NUMBER IS LISTED, CIRCLE WHICH UNIT IS TO BE
 INSTALLED. 2010 FBC- R G2413.2.
 NOTE THIS IS AN ELECTRIC WATER HEATER CHANGE OUT,
 TANKLESS WATER HEATER REQUIRE A HIGHER DEMAND ELECTRIC
 SO THE WIRE SIZING FOR THE NEW UNIT WILL ALSO NEED TO
 BE SIZED.
  
 2) A ELECTRICAL SUB-PERMIT MAY ALSO BE REQUIRED BECAUSE
 OF THE ADDITIONAL DEMAND BEING PUT ON THE EXISSTING
 CIRCUIT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]