Plan Review Notes For Permit 14010549 |
Permit Number |
14010549 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-01-14 08:06:01 | | | PLUMBING PLAN REVIEW | | PERMIT: 14010549 | | ADD: 701 NEW JERSEY ST | | CONT:DON LIPSCOMS PLUMBING | | TEL: (561)310-9245 | | | | 2010 FLORIDA PLUMBING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: TUES. JAN. 14/2014 | | ACTION: DENIED | | | | 1) PROVIDE THE MANUFACTURERS SPEC SHEETS, IF MORE THAN | | ONE MODEL NUMBER IS LISTED, CIRCLE WHICH UNIT IS TO BE | | INSTALLED. 2010 FBC- R G2413.2. | | NOTE THIS IS AN ELECTRIC WATER HEATER CHANGE OUT, | | TANKLESS WATER HEATER REQUIRE A HIGHER DEMAND ELECTRIC | | SO THE WIRE SIZING FOR THE NEW UNIT WILL ALSO NEED TO | | BE SIZED. | | | | 2) A ELECTRICAL SUB-PERMIT MAY ALSO BE REQUIRED BECAUSE | | OF THE ADDITIONAL DEMAND BEING PUT ON THE EXISSTING | | CIRCUIT. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] |
|