2014-01-13 06:54:13 | 1/21/2014 |
| TODAY DESIGNER ALAN BURST CALLED DISCUSSED PROJECT |
| EXISTING OVERHEAD DOORS ARE TO STAY, OKED RED LINING |
| REQUIRED EXIT LIGHT. PASSED. JW |
| |
| |
| |
| |
| |
| |
| BUILDING PLAN REVIEW |
| PERMIT: 14010493 |
| ADD: 219 CLEMATIS ST. |
| CONT: SKYE BLU CONSTRUCTION |
| TEL: (561)935-7584 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JAN. 13/2014 |
| ACTION: DENIED |
| |
| 1) SHEET A2 PLEASE CLARIFY WITHIN THE AREA OF WORK IN |
| THE CREATION OF THE PATIO BAR THE PLANS ARE NOT CLEAR |
| AS TO THE INTENT, IS THIS AREA TO BE USED AS EXTERIOR |
| SEATING, THE TERM PATIO LEADS ONE TO BELIEVE THIS AREA |
| IS EXTERIOR SEATING OR IS THE EXTERIOR GLAZED OVERHEAD |
| DOORS NOT TO BE REMOVED. PLEASE PROVIDE ADDITIONAL |
| INFORMATION. 107.2.1.3. |
| |
| IF THE EXTERIOR OVERHEAD DOORS ARE TO BE REMOVED THEN |
| THIS MAKES THE NEW WALL & OPENINGS PART OF THE EXTERIOR |
| ENVELOPE AS WELL AS THE EXISITNG CEILINGS AND WOULD |
| NEED TO BE DESIGNED TO RESIST WIND PRESSURES ANAD ALSO |
| DEAL WITH COMPONENTS AND CLADDING AS WELL AS INSULATION |
| IN THE NEWLY CONSTRUCTED EXTERIOR WALL. |
| |
| 2) ON NEITHER SHEET A2 NOR THE E SHEETS DOES THERE SHOW |
| EXIT LIGHTS, SINCE THE OCCUPANT LOAD IS OVER 50 (2) |
| EXITS ARE REQUIRED. TABLE 1015.1/ 1006.3.1. |
| |
| 3) IF IN THE ANSWERING OF COMMENT # 1 THIS IS GOING TO |
| NEWLY FORMED EXTERIOR SEATING THEN: |
| 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| TABLE 1609.2(2) . |
| |
| 4) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| |
| 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |