2014-01-10 06:42:45 | PLUMBING PLAN REVIEW |
| PERMIT: 14010249 |
| ADD: 1700 45TH ST SUITE # 1743 |
| CONT: DR ROOTER PLUMBING LLC |
| TEL: (561)628-1953 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: FRI. JAN. 10/ 2014 |
| ACTION: PLUMBING PROVISO APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| DESCRIPTION OF WORK: INSTALLATION OF PORTABLE GREASE |
| TRAP UNDER 3 COMPARTMENT SINK. |
| |
| MET WITH CONTRACTOR BEFORE THE 1ST RESUBMITTAL, HE DID |
| NOT PROVIDE THE SIZE OF THE 3 COMPARTMENT SINK, HE DID |
| NOT PICK WHICH METHOD OF SIZING OF GREASE INTERCEPTOR |
| WAS USED FOR SIZING OF UNIT. MANUFACTURERS SPEC IS FROM |
| BK RESOURCES MODEL BK-GT-30. WITH A CAP FLOW RATE OF 15 |
| G. P.M. |
| |
| 2010FBC-P 1003.3.4.1 GREASE INTERCEPTOR CAPACITY. |
| GREASE INTERCEPTORS AND GREASE TRAPS SHALL HAVE THE |
| GREASE RETENTION CAPACITY INDICATED IN TABLE 1003.3.4.1 |
| FOR THE FLOW-THROUGH RATES INDICATED. |
| |
| NOTE IF SIZING USING THE DFU-METHOD DRAINAGE FIXTURE |
| UNITS THIS GREASE INTERCEPTOR IS SIZED PROPERLY. |
| |