2014-01-08 07:50:22 | PLUMBING PLAN REVIEW |
| PERMIT: 14010249 |
| ADD: 1700 45TH ST # 1743 |
| CONT: DR ROOTER PLUMBING LLC |
| TEL: (561)628-0256 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JAN.08/ 2014 |
| ACTION: DENIED |
| |
| DESCRIPTION OF WORK: INSTALLATION OF PORTABLE GREASE |
| TRAP UNDER 3 COMPARTMENT SINK. |
| |
| 1A) 2010 FBC-PLUMBING 1003.3.4 GREASE INTERCEPTORS AND |
| AUTOMATIC GREASE REMOVAL DEVICES. |
| GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE |
| INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS |
| AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED |
| IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| |
| 1B) PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE GREASE |
| INTERCEPTOR TO BE INSTALLED. * 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 2010 EDITION 107.3.5.1.3 PLUMBING (11) |
| GREASE INTERCEPTORS MINIMUM REQUIREMENTS FOR PLUMBING |
| COMMERCIAL PLAN REVIEW. |
| |
| 2) 2010 FBC-P 1003.3.4.1 GREASE INTERCEPTOR CAPACITY. |
| GREASE INTERCEPTORS AND GREASE TRAPS SHALL HAVE THE |
| GREASE RETENTION CAPACITY INDICATED IN TABLE 1003.3.4.1 |
| FOR THE FLOW-THROUGH RATES INDICATED. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |