Plan Review Notes
Plan Review Notes For Permit 14010226
Permit Number 14010226
Review Stop M
Sequence Number 2
Notes
Date Text
2014-03-26 17:41:51MECHANICAL PLAN REVIEW
 PERMIT: 14010226
 ADD: 319 CLEMATIS ST SUITE # 112
 CONT: CLAY KOHLMEYER
 TEL: (561) 627-3190
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MARCH 26/2014
  
 MECHANICAL PROVISO:
  
 1) HOOD TO BE REVIEWED UNDER A SEPARATE PERMIT WITH
 PLANS.
  
 2)MECHANICAL APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 2A) PROVIDE PRODUCT APPROVALS FOR THE A/C CONDENSATE
 STAND PER RULE 9N-3 FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(G PRE-ENGINEERED A/C STANDS.
  
 2B) FANSKSF-1 & KEF-1 PROVIDE CURB DETAILS, ATTACHMENT
 DETAILS AND ASSOCIATED PRESSURES.
  
 PLUMBING PROVISO:
  
 1) A SEPARATE PERMIT IS REQUIRED FOR A GREASE
 INTERCEPTOR. PROVIDE A CURRENT SIZING METHOD 2010 FBC-P
 1003.3.4 FOR THE GREASE INTERCEPTOR. PDI G101
 TABLE A1.7 IS NO LONGER CURRENT, NOT SINCE THEY DID
 UPDATES IN 2006.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]