2014-02-01 10:08:29 | PLUMBING PLAN REVIEW |
| PERMIT: 14010226 |
| ADD: 319 CLEMATIS ST SUITE # 112 |
| CONT: CLAY KOHLMEYER |
| TEL: (561) 627-3190 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW PLUMBING |
| DATE: FEB. 01/2014 |
| ACTION: DENIED |
| |
| 1) SHEET P-2: |
| |
| 1A) WITHIN THE SERVICE WORK AREA THERE IS A FLOOR SINK |
| LOCATED ADJACENT TO A ICE MAKER, WILL THE COOLER AND |
| FREEZER ALSO DRAIN INTO THE SAME FLOOR SINK? WOULD |
| THERE BE ANY OTHER APPLIANCES DRAINING INTO THIS FLOOR |
| SINK? 2010 FBC-P 709.4.1 CLEAR-WATER WASTE RECEPTORS. |
| WHERE WASTE RECEPTORS SUCH AS FLOOR DRAINS, FLOOR SINKS |
| AND HUB DRAINS RECEIVE ONLY CLEAR-WATER WASTE FROM |
| DISPLAY CASES, REFRIGERATED DISPLAY CASES, ICE BINS, |
| COOLERS AND FREEZERS, SUCH RECEPTORS SHALL HAVE A |
| DRAINAGE FIXTURE UNIT VALUE OF ONE-HALF. |
| 709.3 VALUES FOR CONTINUOUS AND SEMICONTINUOUS FLOW. |
| DRAINAGE FIXTURE UNIT VALUES FOR CONTINUOUS AND |
| SEMICONTINUOUS FLOW INTO A DRAINAGE SYSTEM SHALL BE |
| COMPUTED ON THE BASIS THAT 1 GPM (0.06 L/S) OF FLOW IS |
| EQUIVALENT TO TWO FIXTURE UNITS. |
| |
| 1B) PLEASE SEE THE PREP SINK BY THE MIXER, THIS ISNK IS |
| NOT IDENTIFIED IN THE PLUMBING FIXTURE SCHEDULE NOR IS |
| IT SHOWN ON THE FLAT OR ISOMETRIC WASTE DIAGRAM. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 1C) DIRECTLY EAST OF THE MAIN DOUBLE DOOR ENTRY THE |
| PLANS INDICATE A ICE BEN AND REFRIGARATOR, THE PLANS |
| ARE MISSING A FLOOR SINK OR HUB DRAIN FOR THE ICE BEN, |
| DEPENDING ON THE REFRIGARATOR THERE MAY BE A EVAPORATOR |
| NOT NEEDING A FLOOR DRAIN. 2010 FBC-P 709.4.1 |
| CLEAR-WATER WASTE RECEPTORS. WHERE WASTE RECEPTORS SUCH |
| AS FLOOR DRAINS, FLOOR SINKS AND HUB DRAINS RECEIVE |
| ONLY CLEAR-WATER WASTE FROM DISPLAY CASES, REFRIGERATED |
| DISPLAY CASES, ICE BINS, COOLERS AND FREEZERS, SUCH |
| RECEPTORS SHALL HAVE A DRAINAGE FIXTURE UNIT VALUE OF |
| ONE-HALF. |
| |
| 1D) JUST TO THE LEFT OF THE RESTROOM THERE IS A NOTE |
| FOR THE CONTRACTOR TO VERIFY THE INVERT AND TO CONFIRM |
| THERE IS SUFFICIENT FALL FOR THE NEW FIXTURES, THE |
| SHEET A-1.0 INDICATES THIS TO BE A CONCRETE COLUMN, ARE |
| THE WASTE AND VENT ENCASED IN CONCRETE OR IS THERE A |
| CHASE? 107.2.1.3 ADDITIONA LINFORMATION REQUIRED. |
| |
| 1E) NOTES FROM THE BUILDING REVIEW REQUEST A SEATING |
| PLAN FOR LIFE SAFETY, THE PLUMBING REVIEW WILL ALSO USE |
| THIS PLAN FOR DETERMINING COMPLIANCE WITH 403.2 |
| SEPERATE FACILITIES |
| EXCEPTION # 3 STATES SEPARATE FACILITIES SHALL NOT BE |
| REQUIRED IN BUSINESS AND MERCANTILE OCCUPANCIES WITH A |
| TOTAL FLOOR AREA OF 3,000 SQUARE FEET (279 M2) OR LESS. |
| |
| IF THE NEW LIFE SAFETY PLAN SHOWS MORE THAN 10 SEATS |
| THEY WILL NEED TO COMPLY WITH EXCEPTION # 2 SEPARATE |
| FACILITIES SHALL NOT BE REQUIRED FOR FOOD SERVICE |
| ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS. |
| |
| 1F) THE PLUMBING TABLES SET UP UNDER THE HEADING TABLE |
| 403.1FOR A A2 OCCUPANCY (RESTARAUNT) REQUIRE A SERVICE |
| SINK, THE SAME TABLE UNDER A M (MERCANTILE) OCCUPANCY |
| DO NOT |
| REQUIRE A SERVICE SINK, UNDER THE DEFINITION OF |
| ASSEMBLY OCCUPANCY IT INCLUDES FOR THE CONSUMPTION OF |
| FOOD OR DRINK, THE BUILDING OFFICIAL SHALL DETERMINE |
| FOR THIS USAGE IF A SERVICE SINK IS REQUIRED OR NOT. |
| |
| 1G) PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION ON |
| THE UNDER COUNTER GREASE INTERCEPTOR AND FLOW RATE |
| DEVICE, PLEASE NOTE THE FLOW RATE DEVICE SHALL BE |
| VENTED. |
| 2010 FBC-1003.3.4.2 RATE OF FLOW CONTROLS. |
| GREASE INTERCEPTORS AND GREASE TRAPS SHALL BE EQUIPPED |
| WITH DEVICES TO CONTROL THE RATE OF WATER FLOW SO THAT |
| THE WATER FLOW DOES NOT EXCEED THE RATED FLOW. THE |
| FLOW-CONTROL DEVICE SHALL BE VENTED AND TERMINATE NOT |
| LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD RIM LEVEL |
| OR BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S |
| INSTRUCTIONS. |
| |
| 1003.2 APPROVAL. |
| THE SIZE, TYPE AND LOCATION OF EACH INTERCEPTOR AND OF |
| EACH SEPARATOR SHALL BE APPROVED BY THE PLUMBING |
| OFFICIAL. WHERE THE INTERCEPTOR OR SEPARATOR IS LOCATED |
| WITHIN AN ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEM, |
| SUCH INTERCEPTOR OR SEPARATOR SHALL BE APPROVED BY THE |
| HEALTH OFFICIAL. THE INTERCEPTOR OR SEPARATOR SHALL BE |
| DESIGNED AND INSTALLED IN ACCORDANCE WITH THE |
| MANUFACTURER?S INSTRUCTIONS AND THE REQUIREMENTS OF |
| THIS SECTION. WASTES THAT DO NOT REQUIRE TREATMENT OR |
| SEPARATION SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR |
| OR SEPARATOR. |
| |
| 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC GREASE |
| REMOVAL DEVICES. |
| GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE |
| INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS |
| AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED |
| IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |