2014-02-01 10:08:29PLUMBING PLAN REVIEW
 PERMIT: 14010226
 ADD: 319 CLEMATIS ST SUITE # 112
 CONT: CLAY KOHLMEYER
 TEL: (561) 627-3190
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW PLUMBING
 DATE: FEB. 01/2014
 ACTION: DENIED
  
 1) SHEET P-2:
  
 1A) WITHIN THE SERVICE WORK AREA THERE IS A FLOOR SINK
 LOCATED ADJACENT TO A ICE MAKER, WILL THE COOLER AND
 FREEZER ALSO DRAIN INTO THE SAME FLOOR SINK? WOULD
 THERE BE ANY OTHER APPLIANCES DRAINING INTO THIS FLOOR
 SINK? 2010 FBC-P 709.4.1 CLEAR-WATER WASTE RECEPTORS.
 WHERE WASTE RECEPTORS SUCH AS FLOOR DRAINS, FLOOR SINKS
 AND HUB DRAINS RECEIVE ONLY CLEAR-WATER WASTE FROM
 DISPLAY CASES, REFRIGERATED DISPLAY CASES, ICE BINS,
 COOLERS AND FREEZERS, SUCH RECEPTORS SHALL HAVE A
 DRAINAGE FIXTURE UNIT VALUE OF ONE-HALF.
 709.3 VALUES FOR CONTINUOUS AND SEMICONTINUOUS FLOW.
 DRAINAGE FIXTURE UNIT VALUES FOR CONTINUOUS AND
 SEMICONTINUOUS FLOW INTO A DRAINAGE SYSTEM SHALL BE
 COMPUTED ON THE BASIS THAT 1 GPM (0.06 L/S) OF FLOW IS
 EQUIVALENT TO TWO FIXTURE UNITS.
  
 1B) PLEASE SEE THE PREP SINK BY THE MIXER, THIS ISNK IS
 NOT IDENTIFIED IN THE PLUMBING FIXTURE SCHEDULE NOR IS
 IT SHOWN ON THE FLAT OR ISOMETRIC WASTE DIAGRAM.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) DIRECTLY EAST OF THE MAIN DOUBLE DOOR ENTRY THE
 PLANS INDICATE A ICE BEN AND REFRIGARATOR, THE PLANS
 ARE MISSING A FLOOR SINK OR HUB DRAIN FOR THE ICE BEN,
 DEPENDING ON THE REFRIGARATOR THERE MAY BE A EVAPORATOR
 NOT NEEDING A FLOOR DRAIN. 2010 FBC-P 709.4.1
 CLEAR-WATER WASTE RECEPTORS. WHERE WASTE RECEPTORS SUCH
 AS FLOOR DRAINS, FLOOR SINKS AND HUB DRAINS RECEIVE
 ONLY CLEAR-WATER WASTE FROM DISPLAY CASES, REFRIGERATED
 DISPLAY CASES, ICE BINS, COOLERS AND FREEZERS, SUCH
 RECEPTORS SHALL HAVE A DRAINAGE FIXTURE UNIT VALUE OF
 ONE-HALF.
  
 1D) JUST TO THE LEFT OF THE RESTROOM THERE IS A NOTE
 FOR THE CONTRACTOR TO VERIFY THE INVERT AND TO CONFIRM
 THERE IS SUFFICIENT FALL FOR THE NEW FIXTURES, THE
 SHEET A-1.0 INDICATES THIS TO BE A CONCRETE COLUMN, ARE
 THE WASTE AND VENT ENCASED IN CONCRETE OR IS THERE A
 CHASE? 107.2.1.3 ADDITIONA LINFORMATION REQUIRED.
  
 1E) NOTES FROM THE BUILDING REVIEW REQUEST A SEATING
 PLAN FOR LIFE SAFETY, THE PLUMBING REVIEW WILL ALSO USE
 THIS PLAN FOR DETERMINING COMPLIANCE WITH 403.2
 SEPERATE FACILITIES
 EXCEPTION # 3 STATES SEPARATE FACILITIES SHALL NOT BE
 REQUIRED IN BUSINESS AND MERCANTILE OCCUPANCIES WITH A
 TOTAL FLOOR AREA OF 3,000 SQUARE FEET (279 M2) OR LESS.
  
 IF THE NEW LIFE SAFETY PLAN SHOWS MORE THAN 10 SEATS
 THEY WILL NEED TO COMPLY WITH EXCEPTION # 2 SEPARATE
 FACILITIES SHALL NOT BE REQUIRED FOR FOOD SERVICE
 ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS.
  
 1F) THE PLUMBING TABLES SET UP UNDER THE HEADING TABLE
 403.1FOR A A2 OCCUPANCY (RESTARAUNT) REQUIRE A SERVICE
 SINK, THE SAME TABLE UNDER A M (MERCANTILE) OCCUPANCY
 DO NOT
 REQUIRE A SERVICE SINK, UNDER THE DEFINITION OF
 ASSEMBLY OCCUPANCY IT INCLUDES FOR THE CONSUMPTION OF
 FOOD OR DRINK, THE BUILDING OFFICIAL SHALL DETERMINE
 FOR THIS USAGE IF A SERVICE SINK IS REQUIRED OR NOT.
  
 1G) PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION ON
 THE UNDER COUNTER GREASE INTERCEPTOR AND FLOW RATE
 DEVICE, PLEASE NOTE THE FLOW RATE DEVICE SHALL BE
 VENTED.
 2010 FBC-1003.3.4.2 RATE OF FLOW CONTROLS.
 GREASE INTERCEPTORS AND GREASE TRAPS SHALL BE EQUIPPED
 WITH DEVICES TO CONTROL THE RATE OF WATER FLOW SO THAT
 THE WATER FLOW DOES NOT EXCEED THE RATED FLOW. THE
 FLOW-CONTROL DEVICE SHALL BE VENTED AND TERMINATE NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD RIM LEVEL
 OR BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS.
  
 1003.2 APPROVAL.
 THE SIZE, TYPE AND LOCATION OF EACH INTERCEPTOR AND OF
 EACH SEPARATOR SHALL BE APPROVED BY THE PLUMBING
 OFFICIAL. WHERE THE INTERCEPTOR OR SEPARATOR IS LOCATED
 WITHIN AN ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEM,
 SUCH INTERCEPTOR OR SEPARATOR SHALL BE APPROVED BY THE
 HEALTH OFFICIAL. THE INTERCEPTOR OR SEPARATOR SHALL BE
 DESIGNED AND INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS AND THE REQUIREMENTS OF
 THIS SECTION. WASTES THAT DO NOT REQUIRE TREATMENT OR
 SEPARATION SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR
 OR SEPARATOR.
  
 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES.
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  