2014-02-06 13:21:40BY RL
  
 14010226
 317 CLEMATIS STREET
 INTERIOR CHANGE OF USE TO CAFE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE GFCI PROTECTED RECEPTACLE FOR SERVICING THE
 ROOF TOP AIR CONDITIONING EQUIPMENT. NEC 210.63
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS AND
 WITHIN BATHROOMS AND OUTDOORS MUST BE GFCI PROTECTED.
 NEC 210.8
  
 PROVIDE SHOW WINDOW LIGHTING OUTLETS ABOVE THE WINDOWS.
 NEC 210.62
  
 CLARIFY THE PLANS FOR PHASE AND VOLTAGE. THE PANELS ARE
 SHOWN AS 208 VOLTS AND AS 240 VOLTS. VERIFY THE
 EXISTING SERVICE AND FEEDERS ARE AVAILABLE AS SHOWN.
 NEC 215.5
  
 PROVIDE A SUMMARY LOAD CALCULATION. INCLUDE A CIRCUIT
 AND LOAD FOR THE WATER HEATER. VERIFY THE EXISTING
 SERVICE IS ADEQUATE TO SUPPLY THE NEW RESTAURANT. NEC
 230.31; 220.14; 220.40
  
 VERIFY THE REQUIRED SAFETY LABELING FOR FLASH
 PROTECTION FOR THE ELECTRIC SERVICE, PANEL BOARD AND
 MAIN DISCONNECTING MEANS IS IN PLACE. NEC 110.22,
 110.16, 110.22
  
 VERIFY THE WATER HEATER HAS THE REQUIRED ELECTRIC
 DISCONNECT. NEC 422.31
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 ADD THE EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK
 UP TO THE LIGHTING SCHEDULE. FBC, ENERGY CONSERVATION
 502.3.8; FBC 1011
  
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE
 ALARM SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
  
  