| INTERIOR CHANGE OF USE TO CAFE |
| |
| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| REVIEW COMMENTS. |
| |
| PROVIDE GFCI PROTECTED RECEPTACLE FOR SERVICING THE |
| ROOF TOP AIR CONDITIONING EQUIPMENT. NEC 210.63 |
| |
| ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS AND |
| WITHIN BATHROOMS AND OUTDOORS MUST BE GFCI PROTECTED. |
| NEC 210.8 |
| |
| PROVIDE SHOW WINDOW LIGHTING OUTLETS ABOVE THE WINDOWS. |
| NEC 210.62 |
| |
| CLARIFY THE PLANS FOR PHASE AND VOLTAGE. THE PANELS ARE |
| SHOWN AS 208 VOLTS AND AS 240 VOLTS. VERIFY THE |
| EXISTING SERVICE AND FEEDERS ARE AVAILABLE AS SHOWN. |
| NEC 215.5 |
| |
| PROVIDE A SUMMARY LOAD CALCULATION. INCLUDE A CIRCUIT |
| AND LOAD FOR THE WATER HEATER. VERIFY THE EXISTING |
| SERVICE IS ADEQUATE TO SUPPLY THE NEW RESTAURANT. NEC |
| 230.31; 220.14; 220.40 |
| |
| VERIFY THE REQUIRED SAFETY LABELING FOR FLASH |
| PROTECTION FOR THE ELECTRIC SERVICE, PANEL BOARD AND |
| MAIN DISCONNECTING MEANS IS IN PLACE. NEC 110.22, |
| 110.16, 110.22 |
| |
| VERIFY THE WATER HEATER HAS THE REQUIRED ELECTRIC |
| DISCONNECT. NEC 422.31 |
| |
| PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING |
| COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 |
| |
| ADD THE EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK |
| UP TO THE LIGHTING SCHEDULE. FBC, ENERGY CONSERVATION |
| 502.3.8; FBC 1011 |
| |
| |
| NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE |
| ALARM SYSTEMS, SECURITY AND DATA SYSTEMS. |
| |