Plan Review Notes
Plan Review Notes For Permit 14010213
Permit Number 14010213
Review Stop E
Sequence Number 1
Notes
Date Text
2014-01-14 17:56:52THESE PLANS WERE CONDITIONALLY APPROVED AS FOLLOWS:
 (A TIP TO THE CONTRACTOR) IT IS IN YOUR BEST INTEREST
 TO WAIT TILL ALL THE REVIEWS ARE COMPLETED BEFORE YOU
 SUBMIT A CORRECTION. THE RE-SUBMITTAL WOULD HAVE FAILED
 FOR THE ITEM NOTED, AND THE PLANS WOULD HAVE HAD TO BE
 RESUBMITTED WHEN CORRECTED. I WILL NOT DO THIS NEXT
 TIME)
 AS STATED IN NFPA 72 2007 EDITION SECTION 5.13.6, THE
 MANUAL PULL STATIONS SHALL BE WITHIN 5 FT. OF THE DOOR.