2014-01-08 14:44:35 | REVISION REQUIRED | | 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLAN | | PER TABLE 403.3 FBC (M) 2010 | | 2) SHOW FRESH AIR DUCT ON THE PLAN. PER | | SECTION 107 FBC 2010 | | 3) REFER TO SECTION 503.2.4.4 SHUTOFF | | DAMPER CONTROLS FLORIDA ENERGY CODE 2010 | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|