2014-01-08 14:44:35REVISION REQUIRED
 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLAN
 PER TABLE 403.3 FBC (M) 2010
 2) SHOW FRESH AIR DUCT ON THE PLAN. PER
 SECTION 107 FBC 2010
 3) REFER TO SECTION 503.2.4.4 SHUTOFF
 DAMPER CONTROLS FLORIDA ENERGY CODE 2010