Plan Review Notes For Permit 13121128
Permit Number 13121128
Review Stop P
Sequence Number 1
Notes
Date Text
2014-01-16 18:19:352010 FBC
  
 DENIED BY PLUMBING
  
 1) A PLUMBING SUB PERMIT IS REQUIRED.
  
 2) SUBMIT 2 COPIES OF A POOL PIPING DRAWING SHOWING THE
 PIPE SIZES AND THE PIPE ROUTING TO THE NEW HEATER AND
 THE EXISTING POOL EQUIPMENT. CITY AMENDMENTS 107.1
  
 3) PROVIDE AN ANCHORING DETAIL FOR THE POOL HEATER.
 SPECIFY THE PAD AND HOW THE HEATER WILL BE ANCHORED TO
 IT TO RESIST THE 170 MPH WINDSPEED. FBCR 301.1
  
 4) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION SEC.
 403.9.2 FOR THE REQUIRED TIME SWITCH TO CONTROL THE
 POOL HEATER.
  
 5) A POOL COVER IS REQUIRED BY FBC ENERGY CONSERVATION
 SEC. 403.9.3 FOR HEATED POOLS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]