Plan Review Notes For Permit 13121128 |
Permit Number |
13121128 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-01-16 17:51:17 | 2010 FBC | | | | GAS REVIEW IS DENIED | | | | 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER FBC | | 2010 FUEL GAS. | | | | 2) SHOW TYPE OF PIPING MATERIAL BEING INSTALLED AND ALL | | PIPE SIZES. | | | | 3) SPECIFY TYPE OF GAS (LP OR NATURAL) | | | | 4) SPECIFY THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | BTU LOAD ON THE SYSTEM. REFER TO THE 2010 FBC FUEL GAS | | SPECS. 401.8 THRU 402.6.1 / G2412.8 THRU G2413.6.1 AND | | TABLES 402.4(1) THRU 402.4 (35) / G2413.4 (1) THRU | | G2413.4(8). | | | | 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY (METER) | | TO THE MOST REMOTE OUTLET IN THE SYSTEM PER 2010 FBC | | FUEL GAS APPENDIX A - USE OF CAPACITY SECTION A.3.1(4) | | | | 6) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC 2010 | | FUEL GAS SEC. 402.2 & G2413.2. IF NATURAL GAS SPECIFY | | .5 PSI OR 2 PSI. | | | | 7) SUBMIT MANUFACTURER'S SPEC. SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | NFPA 58 AND FUEL GAS SEC. 402.2 & G2413.2. | | | | 8) THE NAME AND LICENSE NUMBER OF THE PERSON | | RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS. | | CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|