Plan Review Notes
Plan Review Notes For Permit 13121128
Permit Number 13121128
Review Stop G
Sequence Number 1
Notes
Date Text
2014-01-16 17:51:172010 FBC
  
 GAS REVIEW IS DENIED
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER FBC
 2010 FUEL GAS.
  
 2) SHOW TYPE OF PIPING MATERIAL BEING INSTALLED AND ALL
 PIPE SIZES.
  
 3) SPECIFY TYPE OF GAS (LP OR NATURAL)
  
 4) SPECIFY THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2010 FBC FUEL GAS
 SPECS. 401.8 THRU 402.6.1 / G2412.8 THRU G2413.6.1 AND
 TABLES 402.4(1) THRU 402.4 (35) / G2413.4 (1) THRU
 G2413.4(8).
  
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY (METER)
 TO THE MOST REMOTE OUTLET IN THE SYSTEM PER 2010 FBC
 FUEL GAS APPENDIX A - USE OF CAPACITY SECTION A.3.1(4)
  
 6) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC 2010
 FUEL GAS SEC. 402.2 & G2413.2. IF NATURAL GAS SPECIFY
 .5 PSI OR 2 PSI.
  
 7) SUBMIT MANUFACTURER'S SPEC. SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58 AND FUEL GAS SEC. 402.2 & G2413.2.
  
 8) THE NAME AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS.
 CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]