Plan Review Notes
Plan Review Notes For Permit 13121099
Permit Number 13121099
Review Stop E
Sequence Number 1
Notes
Date Text
2014-01-14 16:58:31THE FOLLOWING CORRECTIONS SHALL BE MADE TO THE
 SUBMITTED DRAWINGS FOR THE NEXT REVIEW:
 1. THE MANUAL PULL STATIONS IN RETAIL SPACES 1 & 2 DO
 NOT MEET THE REQUIREMENTS OF SECTION 5.13.7 OF THE 2007
 EDITION OF THE NFPA 72
 2. THE NOTIFICATION APPLIANCES AS INDICATED ON THE
 DRAWINGS FOR CONDO SPACE 111 AND RETAIL SPACES 1 & 2 DO
 NOT MEET THE REQUIREMENTS OF CHAPTER 7 OF THE 2007
 EDITION OF THE NFPA 72
  