2014-01-14 16:58:31 | THE FOLLOWING CORRECTIONS SHALL BE MADE TO THE | | SUBMITTED DRAWINGS FOR THE NEXT REVIEW: | | 1. THE MANUAL PULL STATIONS IN RETAIL SPACES 1 & 2 DO | | NOT MEET THE REQUIREMENTS OF SECTION 5.13.7 OF THE 2007 | | EDITION OF THE NFPA 72 | | 2. THE NOTIFICATION APPLIANCES AS INDICATED ON THE | | DRAWINGS FOR CONDO SPACE 111 AND RETAIL SPACES 1 & 2 DO | | NOT MEET THE REQUIREMENTS OF CHAPTER 7 OF THE 2007 | | EDITION OF THE NFPA 72 | | |
|