2014-01-07 14:52:24 | 344 COURTNEY LAKES CIRCLE |
| PERMIT #13120986 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| *****PROVISO - SUBMIT REVISION***** |
| |
| SUBMIT STAIR, HANDRAIL AND GUARDRAIL DETAILS FOR ACCESS |
| TO THE CONSTRUCTION TRAILER. HANDRAILS ARE REQUIRED ON |
| BOTH SIDES OF THE STAIR. HANDRAILS SHALL BE LOCATED NOT |
| LESS THAN 34 INCHES AND NOT MORE THAN 38 INCHES ABOVE |
| THE SURFACE OF THE TREAD, MEASURED VERTICALLY TO THE |
| TOP OF THE RAIL FROM THE LEADING EDGE OF THE TREAD. |
| HANDRAIL ENDS SHALL BE RETURNED TO THE WALL OR FLOOR OR |
| SHALL TERMINATE AT NEWEL POSTS. HANDRAIL CROSS SECTION |
| SHALL HAVE A DIAMETER OF NOT LESS THAN 1.25 INCHES AND |
| NOT MORE THAN 2 INCHES. |
| GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT |
| THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE, |
| ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN |
| GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER |
| SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR |
| OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT |
| OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH |
| DIAMETER SPHERE. STAIR RISERS SHALL BE BETWEEN 4 INCHES |
| AND 7 INCHES IN HEIGHT. STAIRS SHALL BE SLIP RESISTANT |
| AND HAVE A MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT |
| THE ACCUMULATION OF WATER. |
| |
| PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2 |
| TEMPORARY CONSTRUCTION TRAILERS SHALL BE SEPARATED FROM |
| ADJACENT TRAILERS OR STRUCTURES IN ACCORDANCE WITH |
| TABLE 4.2.1. PER TABLE 4.2.1: |
| 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |
| |