Plan Review Notes
Plan Review Notes For Permit 13120963
Permit Number 13120963
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-12-26 14:48:06326 FERN STREET
 PERMIT #13120963
 MASTER #13030782
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SYSTEM PRESSURES ON THE LOWER LEVELS APPEAR TO EXCEED
 175 PSI. PER NFPA 13 SECTION 8.16.1.2.1 IN PORTIONS OF
 SYSTEMS WHERE ALL COMPONENTS ARE NOT LISTED FOR
 PRESSURE GREATER THAN 175 PSI AND THE POTENTIAL EXISTS
 FOR NORMAL (NONFIRE CONDITION) WATER PRESSURE IN EXCESS
 OF 175 PSI, A LISTED PRESSURE-REDUCING VALVE SHALL BE
 INSTALLED AND SET FOR AN OUTLET PRESSURE NOT EXCEEDING
 165 PSI AT THE MAXIMUM INLET PRESSURE.
  
 PER NFPA 13 (2007 EDITION) SECTION 24.2.1.2, PORTIONS
 OF SYSTEMS NORMALLY SUBJECTED TO SYSTEM WORKING
 PRESSURES IN EXCESS OF 150 PSI SHALL BE TESTED AT A
 PRESSURE OF 50 PSI ABOVE SYSTEM WORKING PRESSURE AND
 SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR 2-HOURS.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 SUBMIT HYDRAULIC CALCULATIONS FOR CLASS I STANDPIPE
 SYSTEM.
  
 NO PRODUCT DATA SUBMITTED FOR TYCO WS SPRINKLERS OR
 FIRE DEPARTMENT VALVES.
  
 I BELIEVE TYCO WS ARE REQUIRED ON BOTH SIDES OF THE
 GLAZING. PLEASE CONFIRM.
  
 TYCO WINDOW SPRINKLERS: IF THE DESIGN INTENT IS TO USE
 TYCO WINDOW SPRINKLERS TO ACHIEVE A FIRE RATED
 SEPARATION, THE SPRINKLERS MUST BE INSTALLED ACCORDING
 TO THE UL LISTING DATA AND SHALL WET THE ENTIRE GLAZING
 SURFACE. SPRINKLERS CANNOT BE USED TO PROTECT OPERABLE
 DOORS OR WINDOWS. THE WINDOW SPRINKLERS DO NOT ALLOW
 HORIZONTAL WINDOW MULLIONS AND REQUIRE THE GLASS
 CURTAIN WALL TO BE ATTACHED TO A THREE FOOT HIGH PONY
 WALL TO KEEP COMBUSTIBLE MATERIALS AT LEAST TWO INCHES
 AWAY FROM THE GLAZING. PAY SPECIAL ATTENTION TO THE
 GLAZING ASSEMBLY AS THE SPRINKLER POSITIONING VARIES
 FOR BUTT-GLAZED INSTALLATIONS COMPARED TO VERTICAL
 MULLION INSTALLATIONS. VERTICAL MULLIONS SHALL BE OF A
 DEPTH THAT PREVENTS COLD SOLDERING OF ADJACENT
 SPRINKLERS. THE SPRINKLER DESIGN SHOULD INDICATE WHICH
 WINDOW SPRINKLER MODEL WILL BE USED (HORIZONTAL
 SIDEWALL OR PENDENT VERTICAL SIDEWALL).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  