Plan Review Notes
Plan Review Notes For Permit 13120954
Permit Number 13120954
Review Stop M
Sequence Number 1
Notes
Date Text
2014-03-03 17:44:572010 FBC
  
 MECHANICAL IS DENIED
  
 1) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS
 AS REQUIRED BY FBCR M1401.3.
  
 2) SPECIFY THE CFMS AT EACH SUPPLY OUTLET. CITY
 AMENDMENTS 107.3.5.3
  
 3) THE RETURN AIR TRANSFER DUCTS ARE UNDER SIZED. FBCR
 M1602.4 BALANCED RETURN AIR REQUIRES THE TRANSFER DUCTS
 TO BE 1.5 TIMES THE CROSS-SECTIONAL AREA OF THE SUPPLY
 DUCT ENTERING THE ROOM AND THE DOOR HAVING AT LEAST A
 ONE INCH UNDERCUT.
  
 4) THE ADDRESS OF THE PROJECT, THE NAME AND LICENSE
 NUMBER OF THE PERSON RESPONSIBLE FOR THE DESIGN IS
 REQUIRED ON THE MECHANICAL PLANS. CITY AMENDMENTS
 107.2.1
  
 5) THE AIR-HANDLER APPEARS TO BE LOCATED IN A CLOSET.
 SPECIFY THE RETURN GRILL SIZE AND LOCATION OR IF THE
 CLOSET HAS A LOUVERED DOOR. CITY AMENDMENTS 107.3.5.3
  