Plan Review Notes For Permit 13120954 |
Permit Number |
13120954 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-03-03 17:44:57 | 2010 FBC | | | | MECHANICAL IS DENIED | | | | 1) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS | | AS REQUIRED BY FBCR M1401.3. | | | | 2) SPECIFY THE CFMS AT EACH SUPPLY OUTLET. CITY | | AMENDMENTS 107.3.5.3 | | | | 3) THE RETURN AIR TRANSFER DUCTS ARE UNDER SIZED. FBCR | | M1602.4 BALANCED RETURN AIR REQUIRES THE TRANSFER DUCTS | | TO BE 1.5 TIMES THE CROSS-SECTIONAL AREA OF THE SUPPLY | | DUCT ENTERING THE ROOM AND THE DOOR HAVING AT LEAST A | | ONE INCH UNDERCUT. | | | | 4) THE ADDRESS OF THE PROJECT, THE NAME AND LICENSE | | NUMBER OF THE PERSON RESPONSIBLE FOR THE DESIGN IS | | REQUIRED ON THE MECHANICAL PLANS. CITY AMENDMENTS | | 107.2.1 | | | | 5) THE AIR-HANDLER APPEARS TO BE LOCATED IN A CLOSET. | | SPECIFY THE RETURN GRILL SIZE AND LOCATION OR IF THE | | CLOSET HAS A LOUVERED DOOR. CITY AMENDMENTS 107.3.5.3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|