2014-03-03 18:41:132010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) SUBMIT TWO COPIES OF ELECTRICAL LOAD CALCULATIONS.
 NEC 408.30
  
 2) SUBMIT TWO COPIES OF A PANEL SCHEDULE AND SPECIFY
 THE AIC RATING OF THE NEW EQUIPMENT. NEC 408.4 AND
 110.9
  
 3) SPECIFY THE LOCATION OF THE METER AND THE PANEL ON
 THE PLANS. CITY AMENDMENTS 107.2.1 AND NEC 240.24
  
 4) SHOW THE LOCATIONS OF THE DISCONNECTS FOR THE NEW
 A/C EQUIPMENT AND THE EQUIPMENT SERVICING RECEPTACLE
 OUTLET. NEC 440.14 AND 210.63
  
 5) PROVIDE THE NAME AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE DESIGN ON THE ELECTRICAL PLANS.
 CITY AMENDMENTS 107.2.1
  