Plan Review Notes For Permit 13120954 |
Permit Number |
13120954 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-03-03 18:41:13 | 2010 FBC / 2008 NEC | | | | DENIED BY ELECTRICAL | | | | 1) SUBMIT TWO COPIES OF ELECTRICAL LOAD CALCULATIONS. | | NEC 408.30 | | | | 2) SUBMIT TWO COPIES OF A PANEL SCHEDULE AND SPECIFY | | THE AIC RATING OF THE NEW EQUIPMENT. NEC 408.4 AND | | 110.9 | | | | 3) SPECIFY THE LOCATION OF THE METER AND THE PANEL ON | | THE PLANS. CITY AMENDMENTS 107.2.1 AND NEC 240.24 | | | | 4) SHOW THE LOCATIONS OF THE DISCONNECTS FOR THE NEW | | A/C EQUIPMENT AND THE EQUIPMENT SERVICING RECEPTACLE | | OUTLET. NEC 440.14 AND 210.63 | | | | 5) PROVIDE THE NAME AND LICENSE NUMBER OF THE PERSON | | RESPONSIBLE FOR THE DESIGN ON THE ELECTRICAL PLANS. | | CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|