Plan Review Notes
Plan Review Notes For Permit 13120869
Permit Number 13120869
Review Stop B
Sequence Number 1
Notes
Date Text
2014-01-03 14:28:522010 FBC
  
 DENIED BY BUILDING
  
 1) THE PLANS ARE REQUIRED TO BE SIGNED, SEALED AND
 DATED BY THE ENGINEER (LARRY M. SMITH FL PE 45997) THAT
 IS LISTED IN THE TITLE BLOCK. FS 471 AND FAC
 61G15-23.002
  
 2) SPECIFY THE WIND LOAD DESIGN CRITERIA FOR THE
 EQUIPMENT SUPPORT STANDS ON THE PLANS. FBC 1609.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]