Plan Review Notes For Permit 13120869 |
Permit Number |
13120869 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-01-03 14:28:52 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE PLANS ARE REQUIRED TO BE SIGNED, SEALED AND | | DATED BY THE ENGINEER (LARRY M. SMITH FL PE 45997) THAT | | IS LISTED IN THE TITLE BLOCK. FS 471 AND FAC | | 61G15-23.002 | | | | 2) SPECIFY THE WIND LOAD DESIGN CRITERIA FOR THE | | EQUIPMENT SUPPORT STANDS ON THE PLANS. FBC 1609.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|