Plan Review Notes For Permit 13120825 |
Permit Number |
13120825 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-02-26 10:19:21 | 5731 PREMIER PARK DRIVE | | PERMIT #13120825 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | REPEAT COMMENT - GENERAL: PROVIDE A PLAN SHOWING THE | | PROPOSED LAYOUT OF THE VEHICLES, BELT CONVEYORS, | | EQUIPMENT, ETC. | | | | REPEAT COMMENT - GENERAL: FOR ISSUANCE OF A GENERAL | | BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA | | BUILDING CODE REQUIRES ENGINEER SEALED FIRE PROTECTION | | CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF | | 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA | | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE | | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | POINT OF SERVICE FOR THE WATER SUPPLY, HYDRANT | | LOCATIONS, A LIST OF APPLICABLE NFPA STANDARDS | | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD | | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM | | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP | | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED | | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 |
|