2014-02-22 13:29:47 | BUILDING PLAN REVIEW |
| PERMIT: 13120825 |
| ADD: 5731 PREMIER PARK RD. |
| CONT: ZIRKELBACH CONSTRUCTION |
| TEL: (864)300-1013 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: SAT. FEB. 22/2014 |
| ACTION: DENIED |
| |
| 1A) COMPLIED. |
| THIS PROJECT BEING TILT-WALL CONSTRUCTION WILL REQUIRE |
| A RESIDENT INSPECTOR. 2010 WEST PALM BEACH AMENDMENTS |
| TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 2010 EDITION* 110.3.9 RESIDENT |
| INSPECTOR. |
| SUBMIT INSPECTOR RESUME' AND LICENSE DOCUMENTS TO KEN |
| CONRAD, MANAGER OF THE RESIDENT INSPECTOR PROGRAM. A |
| RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS |
| PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING: |
| - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION |
| - ANY MAJOR STRUCTURAL ALTERATIONS |
| - STRUCTURES IN WHICH THE CONCRETE DESIGN IS BASED ON |
| COMPRESSIVE STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| - BUILDINGS OVER 20,000 SQ FT IN AREA |
| - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF |
| CONSTRUCTION (TILT WALL DESIGN). |
| |
| KEN CONRAD CONTACT INFORMATION: |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| RESIDENT INSPECTOR BOOKLET & FORMS WERE E-MAILED TO |
| ANTHONY CAMPANO AT [email protected] |
| 1/06/2014 07:46 AM. |
| SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| THE RESIDENT INSPECTOR. |
| |
| AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT, |
| SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF |
| COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE |
| WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN |
| ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION |
| SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A |
| CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION |
| IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT |
| ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS. |
| |
| 1B) 2ND REQUEST, SINCE THIS PROJECT WILL REQUIRE A |
| RESIDENT INSPECTOR (3) SETS OF PLANS, AND PRODUCT |
| APPROVALS WILL BE REQUIRED. |
| |
| 2) NOTIFICATION. * 2010 WEST PALM BEACH AMENDMENTS TO |
| THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| 2010 EDITION 110.7 IMPACT OF CONSTRUCTION. ALL |
| CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT |
| GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS |
| OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY |
| OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE |
| CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS, |
| DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW |
| CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL |
| HISTORIC SURFACE |
| WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, AND |
| MAY REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE POSITIVE DRAINAGE |
| PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| DEVELOPERS, CONTRACTORS AND OWNERS OF ALL NEW |
| RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A SIGNIFICANT DECREASE OF |
| PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE |
| DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 3) COMPLIED> |
| THE STRUCTURAL SHEETS ENGINEERS SIGNATURE AND SEAL ARE |
| ALL PHOTO-COPIES. PLANS, SPECIFICATIONS, REPORTS OR |
| OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE |
| AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| DOCUMENT. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS |
| EFFECTIVE DATE 05/06/2009 |
| (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE |
| SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL |
| BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL |
| ENGINEER IN RESPONSIBLE CHARGE. |
| |
| 4) COMPLIED> SHEET S-101 THE WIND DESIGN CRITERIA NEEDS |
| CORRECTIONS, THERE IS A DISCREPANCY BETWEEN THE |
| BUILDING IMPORTANCE FACTOR (BUILDING CATEGORY 2) AND |
| THE WIND VELCITY (160 ULTIMATE). WE AGREE THIS IS A |
| BUILDING CATEGORY 2 BUT WITH A ULTIMATE VELOCITY OF 170 |
| MPH WIND VELOCITY , EXPOSURE C. |
| |
| 5) 2ND REQUEST. |
| MISSING IN THE STRUCTURAL DESIGN ROOF FRAMING AND ROOF |
| DECK DESIGN, PART OF THE BUILDING ENVELOPE. * 2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.3.5.1.1(8) |
| MINIMUM REQUIREMENTS FOR COMMERCIAL PLAN REVIEW, |
| BUILDING ENVELOPE/ ROOF FRAMING/ ROOF SYSTEMS. |
| |
| 6) COMPLIED. |
| |
| 7) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) PRE-ENGINEERED A/C STANDS |
| |
| 8) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 9) 2ND REQUEST. SHEET A1.3 INDICATES THE EGRESS PLAN IS |
| DESIGNED TO THE 2004 FBC-B, 2010 FBC- EXISTING |
| BUILDING. 1001.1 SCOPE. AN ADDITION TO A BUILDING OR |
| STRUCTURE SHALL COMPLY WITH THE FLORIDA BUILDING CODES |
| AS ADOPTED FOR NEW CONSTRUCTION WITHOUT REQUIRING THE |
| EXISTING BUILDING OR STRUCTURE TO COMPLY WITH ANY |
| REQUIREMENTS OF THOSE CODES OR OF THESE PROVISIONS, |
| EXCEPT AS REQUIRED BY THIS CHAPTER. WHERE AN ADDITION |
| IMPACTS THE EXISTING BUILDING OR STRUCTURE, THAT |
| PORTION SHALL COMPLY WITH THIS CODE. |
| |
| 10) SHEET A3.1, CUT SECTION THRU NEW OFFICE WALLS, |
| DETAIL # 2/ A8.2 : |
| 10A) COMPLIED. |
| 2010 FL EXISITNG BLDG CODE 1001.2 CREATION OR EXTENSION |
| OF NONCONFORMITY. AN ADDITION SHALL NOT CREATE OR |
| EXTEND ANY NONCONFORMITY IN THE EXISTING BUILDING TO |
| WHICH THE ADDITION IS BEING MADE WITH REGARD TO |
| ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE SAFETY, MEANS |
| OF EGRESS, OR THE CAPACITY OF MECHANICAL, PLUMBING, OR |
| ELECTRICAL SYSTEMS. |
| THE COVER SHEET NOR A3.1 INDICATE HOW COMPLIANCE WITH |
| OCCUPANCY SEPERATION IS OBTAINED AND COMPLIANCE WITH |
| FBC-B TABLE 508.4. |
| |
| 10B) 2ND REQUEST. THIS DETAIL INDICATES INSULATION IN |
| THE WALL THAT SEPERATES THE STORAGE OCCUPANCY FROM THE |
| OFFICE AREA. 2010 EXIST BLDG CODE LEVEL II ALTERATIONS: |
| 711.1 MINIMUM REQUIREMENTS. ALTERATIONS SUBJECT TO THIS |
| CHAPTER SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, ENERGY CONSERVATION.101.4.1 |
| EXISTING BUILDINGS. |
| EXISTING BUILDINGS SHALL MEET THE CRITERIA IN TABLE |
| 101.4.1 AS APPROPRIATE TO THE CONDITION DESCRIBED. IN |
| TABLE 101.4.1 RENOVATION ENVELOPE TO MEET SECTION 502 . |
| 502.1.1.1 SHELL BUILDINGS, RENOVATIONS AND ALTERATIONS. |
| THE BUILDING THERMAL ENVELOPE SHALL MEET THE |
| REQUIREMENTS OF TABLE 502.1.1.1(1) OR TABLE |
| 502.1.1.1(2) |
| |
| 10C) 2ND REQUEST. PROVIDE COMPLIANCE WITH 2010 ENERGY |
| CODE 502.2.1.2 CEILING INSULATION. INSULATION INSTALLED |
| ON A SUSPENDED CEILING WITH REMOVABLE CEILING TILES |
| SHALL NOT BE CONSIDERED PART OF THE MINIMUM THERMAL |
| RESISTANCE OF THE ROOF INSULATION UNLESS THE |
| ROOF/CEILING CAVITY IS SEALED FROM THE EXTERIOR |
| ENVIRONMENT. |
| 502.3.5.2 UNVENTED DROPPED CEILING CAVITIES. |
| WHERE UNVENTED DROPPED CEILING CAVITIES OCCUR OVER |
| CONDITIONED SPACES THAT DO NOT HAVE AN AIR BARRIER |
| BETWEEN THE CONDITIONED AND UNCONDITIONED SPACE (SUCH |
| AS T-BAR CEILINGS), THEY SHALL BE COMPLETELY SEALED |
| FROM THE EXTERIOR ENVIRONMENT (AT THE ROOF PLANE) AND |
| ADJACENT SPACES BY A CONTINUOUS AIR BARRIER THAT IS |
| ALSO SEALED TO THE AIR BARRIER OF THE WALLS. IN THAT |
| CASE, THE ROOF ASSEMBLY SHALL CONSTITUTE BOTH THE UPPER |
| THERMAL ENVELOPE AND PRESSURE ENVELOPE OF THE BUILDING. |
| |
| 11) 2ND REQUEST. SHEET A1.3 & A2.1 SHOW 2 NEW LOADING |
| DOORS 27 & 28, SHEET A9.2 DETAIL # 3 INDICATES CONCRETE |
| WALL PANELS WHERE DETAIL 1,6 & 10 APPEAR THEY ARE FOR |
| METAL BUILDING? |
| DISCREPANCY IN THE PLANS. 107.2.1.3. ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |