 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE A PLAN SHOWING THE PROPOSED LAYOUT OF
 THE VEHICLES, BELT CONVEYORS, EQUIPMENT, ETC.
  
 SHEET M1.1: PLAN INDICATES TWO CARBON MONOXIDE
 DETECTORS ON THE WEST AND CENTRAL AREA OF THE BUILDING
 ADDITION. AN ADDITIONAL DETECTOR MAY BE NEEDED ON THE
 EAST SIDE OF THE BUILDING.
  
 GENERAL: FOR ISSUANCE OF A GENERAL BUILDING PERMIT,
 SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE
 REQUIRES ENGINEER SEALED FIRE PROTECTION CONSTRUCTION
 DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE
 AUTOMATIC FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, HYDRANT LOCATIONS, A LIST OF APPLICABLE
 NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  