Plan Review Notes For Permit 13120750 |
Permit Number |
13120750 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-01-14 14:36:50 | PLUMBING PROVISO: | | | | SHEET P-5.01 TWO NEW SHOWER DRAINS ARE NOT SIZED, | | FBC-P TABLE 709.1 SHOWER DRAIN IS BASED ON FLOW RATE | | 2" TRAP GREATER THAN 5.7 GPM TO 12.3 GPM | | 3" TRAP GREATER THAN 12.3 GRM TO 25.8 GPM. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] |
|